These installation instructions provide essential information for installing VESDA-E VES Aspirating Smoke Detectors in accordance with the system design. Additional installation and product documentation is listed 
below in the Reference Documents section.

VESDA-E VES Installation Instructions

System Components

The detector is shipped with the following components:

• 

1 aspirating smoke detector

• 

1 mounting bracket

• 

1 mounting template for directly mounting the detector to the mounting surface 

• 

1 End of Line Resistor for the monitored GPI (fitted to terminal)

• 

1 installation instruction sheet

Prerequisites

• 

A completed system design.

• 

A 24V DC Power Supply, compliant with local codes and standards.

• 

Screws and inserts that are appropriate for the mounting suface.

• 

Type A to Type B USB Interface Lead for initial configuration of the detector.

• 

Labels as specified in the system design, e.g. Sampling Point labels.

• 

Cable glands that are compliant with the IP rating of the detector.

• 

Conduit, as specified in the system design.

• 

0.2 mm

2

 to 2.5 mm

2

 (24 - 14 AWG) wiring for relays.

• 

A PC or laptop with Xtralis VSC installed for initial configuration.

Standards Compliance

UL and ULC

 

For open area, open area high velocity and duct protection the fire alarm threshold (setting) that initiates an 

evacuation signal must be set such that the sensitivity of each sampling hole is more sensitive than 10%/m 

(3.2 %/ft) as determined by the ASPIRE software.

Power Consumption (18 - 30 VDC Supply)

Quiescent

In Alarm

Aspirator Speed

Setting 1

Setting 5

Setting 10

Setting 1

Setting 5

Setting 10

VES-A00-P

7.9 W

9.7 W

14.8 W

8.5 W

9.9 W

14.5 W

VES-A10-P

8.6 W

10.5 W

15.4 W

9.4 W

10.8 W

15.2 W

Peak current: 1.5 A

Environmental Requirements

• 

Temperature

 

• 

Ambient:

 0°C to 39°C (32°F to 102°F) *

• 

Tested to: 

(EN54-20): -10°C to 55°C (14°F to 131°F)

• 

Sampled Air:

 -20°C to 60°C (-4°F to 140°F) **

• 

Humidity:

 5% to 95% RH, non-condensing

Note: 

 

Please consult your Xtralis representative for information on operation outside these 

parameters or where sampled air is continually above 0.05% obs/m (0.015% obs/ft) under 

normal operating conditions.

* Product UL listed for use from 0°C to 38°C (32°F to 100°F)

** The sampled air temperature shall be within the Ambient temperature specification at entry into the Detector. 

Refer to Xtralis Design Guides and Application Notes for sampled air pre-conditioning.

Reference Documents

Additional installation and product information is contained in the following documents, which are 
available for download in the Xtralis partner extranet at www.xtralis.com.

• 

33830 - VESDA-E VES-A00-P Product Guide

• 

33794 - VESDA-E VES-A10-P Product Guide

Installation Instructions

Notes

The VESDA-E detector can be mounted in an upright or 
inverted position. Do not mount the detector with a sideways 
orientation.

Ensure the mounting surface is flat as this allows an air tight 

seal to be achieved between the sampling pipe and the 
tapered air inlet pipes on the detector.

Refer to the detector Product Guide for information on 
inverted mounting.

A

B

Ensure that there is sufficient clearance to mount the 

detector, noting the location of air sampling pipes and 
cable entry points. Due to the rigid nature of the plastic 

pipe, installation must provide for sufficient movement in all 

pipework (air inlet, air exhaust and cable pipes) to allow pipe 

ends to be easily fitted and removed.

• 

A:

 

Minimum 50 mm (2 in.) below ceiling level.

• 

B:

 The detector can be mounted directly against a 

wall or obstruction.

Attach the detector to the wall using the mounting bracket

Position the mounting bracket as specified by the system designer

E
F

B

D

A

C

D

G

G

G

G

G

• 

Position the mounting bracket (A) to allow sampling pipes 

(B) and electrical conduit (C) to line up horizontally with the 

alignment marks (D) and vertically with the appropriate pipe 

depth line.
• 

3/4 inch IPS (1.05 inch OD) sampling pipe should vertically 

align with the top depth line (E).

• 

25 mm OD sampling pipe should vertically align with 

the bottom depth line (F).

• 

Hold the plate in position and mark positions for 5 screw 

holes (G) on the mounting surface. Remove the plate and 

drill holes. Insert plugs if required.

Secure the mounting bracket to the mounting surface

B

B

D

D

A

D

C

C

• 

Align the mounting plate with the holes. Ensure that the 
plate is level.

• 

Insert and tighten two screws (B) in the keyhole slots (C) 

followed by three screws (D) in the remaining slots.

• 

Use screws and inserts that are appropriate for the 
mounting surface and the weight of the detector.

Position the detector on the mounting bracket

A

A

A

B

C

• 

Align the mounting studs (A) on the rear of the detector 

with the mounting stud slots on the mounting bracket. 

Ensure that the center stud (B) is in its slot.

• 

Slide the detector (C) down until the top of the detector is 

flush with the top of the mounting bracket.

Secure the detector to the mounting bracket

A

B

C

C

• 

Open the door by inserting a thin screwdriver into hole (B) 

and pushing firmly.

• 

Remove the tape covering the partially inserted locking 

screw (C).

• 

Tighten the locking screw.

Attach the detector directly to the mounting surface

Use the provided mounting template. Refer to the Product Guide for further information.

Note: 

 

Do not remove the mounting studs from the rear of the detector as they are also used to hold 

internal components in place.

Inverted Mounting

Some system designs require that the detector be inverted. Directions for correcting the orientation of the 
fascia for an inverted detector are available in the Product Guide.