background image

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the completeness, accuracy or reliability of the contents of this document. The 

manufacturer reserves the right to change designs or specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied 

warranties of merchantability and fitness for a particular purpose are expressly excluded.

Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO, OSID, HeiTel, ADPRO, IntrusionTrace, LoiterTrace, ClientTrace, SmokeTrace, XOa, XOh, iTrace, iCommand, iRespond, iCommission, 

iPIR, and FMST are trademarks and/or registered trademarks of Xtralis and/or its subsidiaries in the United States and/or other countries. Other brand names mentioned herein are for identification purposes only and 

may be trademarks of their respective holder(s). Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.

This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written 
consent of Xtralis.

www.xtralis.com

UK and Europe

 +44 1442 242 330  

The Americas 

+1 800 229 4434

Middle East 

+962 6 588 5622  

Asia 

+86 21 5240 0077

  Australia and New Zealand

 +61 3 9936 7000

Part: 30917

VESDA-E VES Installation Instructions

Prepare Detector: 

Wiring, Pipe Inlet and Exhaust Ports

Remove the appropriate plugs for electrical cable installation (B), air sampling pipe inlet ports (A), and 

exhaust port (C). 

• 

For VES detectors, where the system design requires less than four air sampling pipe inlet ports, 
use ports 2 and 3 before using ports 1 and 4. 

• 

Do not remove the plugs from inlet ports that will not be used.

• 

Ensure that pipes are clean and their ends are square and smooth.

A

B

B

C

E

D

1

2

3

4

INLETS

A

Inlet Port, Qty 4

B

Cable Entry Port, Qty 4, 26 mm (1”)

C

Exhaust Port, OD 25 mm or 1.05” (3/4” IPS) via adaptor

D

Inlet Pipe Diameter: OD 25 mm or 1.05” (3/4” IPS)

E

Minimum Inlet Pipe Length: 500mm (19.6”) 

• 

Insert the inlet and exhaust pipes (if used) into the correct inlet ports (A) and exhaust port. 

• 

Exhaust pipe should be as short as possible.

• 

Feed the electrical wiring connections through the cable entry ports. 

• 

Use the correct cable gland size to fit into the 26 mm (1”) cable entry port. Use correctly rated cable 

glands to maintain the required IP rating.

Note:  

Do not glue the inlet and exhaust pipe into the detector ports. The product warranty will be 
void if the pipes are glued.

Wiring: 

Power, Relays, GPIs, VESDAnet

Warning:

  

Always switch detector power OFF before plugging/unplugging electrical, relay or network 
connections. Failure to do so may cause data corruption and/or component failure.

Avertissement :

  Eteignez toujours détecteur avant de brancher/débrancher les relais électriques, ou de 

connexions réseau. Au cas contraire vous pouver entraîner la défaillance corruption et/ou 

élément de données.

R

S

T

U

+

-

+

-

A

B

+

-

+

-

C

D

SH

SH

C NO

RL7

C NO

RL5

C NO

RL4

C NO

RL2

C NO

RL1

NC C  NO

RL

 3 U 

FA

UL

T

RL8

C NO

RL9

C NO

RL10

C NO

RL1

1

C NO

RL12

C NO

NC C  NO

RL

 6 FIRE 1

J

I

H

G

F

E

K

L

M

N

O

P

Q

V

Power

A

Power Out

B

Power In

VESDAnet

C

VESDAnet B

D

VESDAnet A

Relays

E

3 - Urgent Fault

F

1 - Disable

G

2 - Minor Fault

H

4 - Alert

I

5 - Action

J

7 - Fire 2

K

8 - First Alarm Sector 1

L

9 - First Alarm Sector 2

M

10 - First Alarm Sector 3

N

11 - First Alarm Sector 4

O

12 - Scanning

P

6 - Fire 1

Communications

R

Ethernet

S

USB

GPI

T

Monitored GPI

U

Unmonitored GPI

Chassis Ground

V

Jumper for ground fault  

monitoring

Q

Chassis Ground Terminal

Power and Relay Wiring

Power:

 There are two sets of power terminals on the main board. Connect a 24 VDC power supply to the 

PWR IN socket (B). If required, connect to another detector via the PWR OUT socket (A).

Relays: 

The relays interface to the Fire Alarm Control Panel (FACP) to communicate faults, alarms and 

disabled states. Relay contacts are rated 2 A @ 30 VDC, resistive. Connect as required by the system 

design. Use electrical wire sizes from 0.2 mm² to 2.5 mm² (24 -14 AWG). 

Warning:  

Ensure that all wiring complies with manufacturer’s instructions and local and national fire 

detection code requirements. Refer to the Codes and Standards Information for Air Sampling 
Smoke Detection section of the detector product guide for further information on wiring 
compliance.

Avertissement :

  Verifier que toute les cables ont passé au nombres d’instructions du fabricant et locaux et au 

feu national de securited’incendie sois exiger. Adresser aux codes informations sur les normes 
et reglementations de detection de fume par prelevement d’air par le notice descriptive du 
produit pour plus de renseignements au conformite du cablage.

Caution:

  

DO NOT LOOP WIRE UNDER TERMINALS WHEN WIRING DETECTORS. BREAK WIRE 
RUNS TO PROVIDE SYSTEM SUPERVISION OF CONNECTIVITY.

Attention :

 

NE PAS RALIER LES CABLES TERMINAUX PENDANT LES CABLAGES DES FILS. POUR 
TOUTES LES CONNECTIONS A RELAIS, INTERROMPRE LES FILS POUR PERMETTRE LA 
SUPERVISION DU CABLAGE.

Note:

  

For information on wiring for other types of devices that may be required by the system 
design, refer to the detector Product Guide and documentation accompanying the device.

Unmonitored GPI

The Unmonitored GPI senses a voltage level and is configurable to initiate a number of different actions. 

“Reset” is the default setting.

Monitored GPI

The monitored GPI senses contact closure and is configurable to initiate the same actions as the 

unmonitored GPI. “Mains OK” is the default setting. A closed contact signals GPI ON and open contact 
signals GPI OFF.

A 10K end of line resistor is used to allow the detector to monitor for open circuit faults in the wiring from 
the detector to the contact.

 

Connection to Addressable Loop Module for Reporting Alarms and Faults

Normally Closed (NC)

Common (C)

Normally Open (NO)

Common (C)

ACTION

Normally Open (NO)

Detector

Fire Input
EOL* = Normal
Short = Fire
Open = Wiring Fault

3 Inputs Loop Module

Pre Alarm
EOL* = Normal
Short = Fire
Open = Wiring Fault

EOL*

EOL*

Relay shown energized which
is the no-fault condition

Normally Closed (NC)

Common (C)

FAULT

Normally Open (NO)

Fault Input
EOL* = Normal

Detector Fault

Short =
Open = Wiring Fault

EOL*

FIRE 1

This wiring example is for wiring VESDA detectors 
to a typical third party Input Loop Module with three 
inputs.

This is an example drawing. Refer to the 
appropriate product manual for the exact wiring 
details of the third party equipment.

* EOL = End of Line Resistor

Connection to VESDAnet

A+

A-

B-

Shield

Module 1

Module 2

Module 3

Module 5

Module 4

Shield

B+

A+

A-

B-

Shield

Shield

B+

A+

A-

B-

Shield

Shield

B+

A+

A-

B-

Shield

Shield

B+

A+

A-

B-

Shield

Shield

B+

The diagram shows an example of the wiring for a 
closed VESDAnet loop, which is the recommended 

configuration. Remove the factory default A and B 

links from the VESDAnet sockets (C and D) prior 

to connecting the detector to the VESDAnet. It is 
recommended that 120 Ohm twisted pair cables 

(e.g. Belden 9841) be used for including the 

devices in the network, with a maximum length 
between devices of 1.2 km The polarity of the data 
wires must be maintained throughout the network.

Standalone Detector

Shield

A-

A+

Shield

B-

B+

The diagram below shows the factory default wiring for VESDAnet sockets (C and D) 

as required for a detector that is not connected to a VESDAnet.

• 

Leave as is, or replace if it has been removed.

Ground Fault Detection

In order for VESDAnet ground fault detection to be active, connect the Chassis Ground Terminal (Q) to the 

building ground and insert a jumper on the Ground Fault Monitoring Jumper terminals (V).

Communications

• 

USB: 

The USB port (S) is used for initial configuration and local maintenance or servicing of the 

detector using a PC or laptop with Xtralis VSC software. Install Xtralis VSC prior to connecting the 
detector to the computer. This ensures that the required USB drivers are present.

• 

Ethernet:

 The Ethernet port (R) is used for permanent network connection to the detector, and 

provides a gateway to other devices on the VESDAnet network. Ethernet connection settings and 

detector access password must be configured using a USB connection prior to use.

• 

WiFi:

 The WiFi provides a network connection to the detector and provides a gateway to other devices 

on the VESDAnet network. WiFi connection settings and detector access password must be configured 

using a USB connection prior to use.

Sampling Pipe Network

Complete the pipe network installation in accordance with the system design. Refer to the detector Product 
Guide and the VESDA Pipe Network Installation Guide for general information regarding pipe network 
installation.

• 

Ensure that the exhaust is open, the pipes are clear and all sampling holes have been drilled.

Power Up

Connect 24 VDC power to the Power In terminals (B). Close front door.

Configuration

For initial configuration, use a USB connection and the Xtralis VSC software.

• 

For networked detectors, set the IP address and subnet mask according to standard building 
instructions.

• 

Set the Pipes in Use value in the Airflow configuration options.

• 

Set the aspirator RPM to the value specified in the system design.

• 

Let the detector run for approximately 2 minutes and confirm that the pipe raw flow rates (L/min) match 

the ASPIRE predictions using Xtralis VSC. 

• 

Normalize the airflow. This takes approximately 10 minutes, after which the pipe flow rates (%) should 

be close to 100%.

• 

Reset the detector. It should now be running without faults.

Commissioning

• 

Carry out a smoke test. Refer to the product guide for further information.

Document: 33831_A0

Note:  

To remove the pipe inlet and cable entry port 
plugs, place a large screwdriver in the large 
slot and twist, or use a small screwdriver in 
the side slots to lever the plug out.