VESDA-E VEP-A10-P Product Guide
64
www.xtralis.com
5.5.8
General Purpose Inputs Options
The General Purpose Inputs options page provides the ability to control the behavior of the Unmonitored and
Monitored General Purpose Inputs (GPIs).
The GPIs can be configured to initiate a number of different actions.
Figure 5-18: General Purpose Input Options
The configuration options are as follows:
l
GPI function (Unmonitored) and GPI function (Monitored):
Refer to Table 5-3 below for a description
of the individual selections.
l
Button Lockout:
If the checkbox is ticked the Reset, Disable and Acknowledge functions can't be
executed using the front panel button.
Function
State Change
External Reset
Unmonitored GPI
The detector resets on a 0 VDC to 5 VDC
rising edge.
Monitored GPI
The detector resets on a contact closure.
Reset
0V
5V
Reset
Open
Closed
Table 5-3: GPI Operation
Содержание VESDA-E VEP-A10-P
Страница 1: ...VEP A10 P 4 Pipes VESDA E VEP A10 P Product Guide September 2020 Doc No 22071_15 Part No AD30311 000 ...
Страница 2: ......
Страница 8: ...VESDA E VEP A10 P Product Guide vi www xtralis com This page is intentionally left blank ...
Страница 12: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 78: ...VESDA E VEP A10 P Product Guide 70 www xtralis com This page is intentionally left blank ...
Страница 96: ...VESDA E VEP A10 P Product Guide 88 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 102: ...VESDA E VEP A10 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Страница 106: ...VESDA E VEP A10 P Product Guide 98 www xtralis com This page is intentionally left blank ...
Страница 112: ...VESDA E VEP A10 P Product Guide 104 www xtralis com Z zone 55 57 73 99 ...