Product Information
2.1
Detector Components
The VEP-A10-P detector contains field-replaceable Filter, Aspirator and Chamber Assembly components.
These are shown below in Figure 2-1.
F
D
C
B
E
Legend
A
Fascia with 3.5"
touchscreen display
B
Filter
C
Chamber Assembly
D
Aspirator
E
Sampling Module
F
Base
Figure 2-1: Detector components
Refer to Chapter 7 for further information regarding maintenance scheduling and availability of spare parts.
2.2
How the VEP-A10-P works
An air sampling pipe network collects samples from the protected area. The integrated aspirator draws air into
the sampling pipe(s).
The air from each sampling pipe passes through an air flow sensor and then a sample of the air is drawn into
the smoke detection chamber via the sampling module, after first passing through the replaceable filter.
A further filter provides filtered clean air to protect the optical surfaces inside the detection chamber from
contamination.
The detection chamber uses a short wavelength laser light source in conjunction with photodiodes and
advanced imaging technology to achieve optimum response to a wide range of smoke types.
If the detected smoke is higher than the set alarm thresholds it is reported as an Alert, Action, Fire 1 or Fire 2
alarm condition.
Air is exhausted from the VEP-A10-P and may be vented back into the protected zone.
Alarms can be signalled via Relays and VESDAnet. Ethernet can be used for configuration and secondary
monitoring, and a USB interface is provided for initial setup.
The detector has a LED plus LCD user interface. A series of LEDs display Alarm, Fault, Disable and detector
power on status. The detector has a buzzer which can be configured to signal alarm, fault, disable and
standby status. A button allows the user to Reset or Disable the detector or to acknowledge status. In
addition an LCD displays detector status including smoke level and a smoke level bar graph, alarm
thresholds, trouble status, % airflow level, normalization status and filter life used.
Содержание VESDA-E VEP-A10-P
Страница 1: ...VEP A10 P 4 Pipes VESDA E VEP A10 P Product Guide September 2020 Doc No 22071_15 Part No AD30311 000 ...
Страница 2: ......
Страница 8: ...VESDA E VEP A10 P Product Guide vi www xtralis com This page is intentionally left blank ...
Страница 12: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 78: ...VESDA E VEP A10 P Product Guide 70 www xtralis com This page is intentionally left blank ...
Страница 96: ...VESDA E VEP A10 P Product Guide 88 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 102: ...VESDA E VEP A10 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Страница 106: ...VESDA E VEP A10 P Product Guide 98 www xtralis com This page is intentionally left blank ...
Страница 112: ...VESDA E VEP A10 P Product Guide 104 www xtralis com Z zone 55 57 73 99 ...