www.xprgroup.com
2
EN
Connection example of 1 door
This product herewith complies with requirements of EMC directive 2014/30/EU.
In addition it complies with RoHS2 directive EN50581:2012 and RoHS3 Directive 2015/863/EU.
Run Led
Box Tamper
Led Comm
Net
Reader
Reader
Door contact
Electromagnetic Lock 12V/600mA max
Adjust the output to 14.2 Vdc,
using screwdriver
Push button
Address 0
Address 1
See user manual
12V battery
Po
w
er S
upply
Batter
y
Po
w
er f
or door lock
Door R
ela
y 1
GND f
or door lock
Door Cont
act 1
Push Button 1
Gnd f
or DC and PB
12 VDC f
or r
eader
RS45 -/R
S-485 B
RS45 -/R
S-485 A
Gnd f
or r
eader
Not used
- For doors equipped with 2 readers, one must be at address 0 and the other at address 1. If there is
only 1 reader, then it is recommended to be put with address 0.
- LIYCY cable, twisted pair, up to 80m. (5)
If more than 80 m. are needed, then termination resistors(120 ohm) may be required at both ends of
the RS-485 line, while taking into consideration the lengths proposed on our web site.
- Alarm cable 2x0,22 (6)
- The cross section of the cable depends on the current needed by the lock (7)
Note:
The elevators relay boards (WS4-RB-12) are connected on the same RS-485 lines as the readers.
OFF
ON
1
Lan
Autonomous
2
Master
Slave
Dip Switch
Diode
1N4001