Technical data:

Technical data

Units

Specification

Voltage / Frequency

V / Hz

~ 220-240V / 50-60 Hz

Max. current consumption

A

0.60

Power consumption - Speeds 1, 2, 3

W

26 / 48 / 80

Air – volume flow rate - Speeds 1, 2, 3

mƒ/h

50 / 100 / 150

Air volume flow rate at 90 Pa Static Pressure

Pa

150m

3

/h

Protection category

IP

20

Max. ambient temperature

„C

50

Dimensions (without ducting) - W x H x D

mm

600 x 595 x 425

Weight of appliance

Kg

17.5

Air connections

mm

125 

Condensate pipe connections

mm

20

Filter class

-

G4

Efficiency of heat exchanger

%

Up to 90%

Sound pressure level (measured at a distance of 1m) - Speeds 1, 2, 3
Sound pressure level (measured at a distance of 3m) - Speeds 1, 2, 3

dB (A)

29.5 / 32.0 / 39.0
20.0 / 22.5 / 29.5

6.6

Applied Energy accessories for manual or automatic operation:

Description

Part 

Number

Notes

MS2 controller

23513AW

The manual 2-speed switch is suitable for the Xcell 150 QV model
only. This switch can be flush or surface mounted. 

QCO

2

controller

96003AA

The CO

2

sensor is suitable for the Xcell 150 QVW model only. 

Only 1 off CO

2

sensor can be used per MVHR unit.

Q3SP controller

96005AA

The automatic 3-speed switch is suitable for the Xcell 150 QVW model 
only. This switch can be flush or surface mounted.

QHS sensor

96009AA

The Humidistat sensor is suitable for the Xcell 150 QVW model only. 

Note:
1.

When using Humidistats in conjunction with the Q3SP 3-speed 
switch a maximum of 4 Humidistats can be connected. 

2.

When using Humidistats in conjunction with the Q3SP 3-speed 
switch and a CO

2

sensor a maximum of 3 Humidistats can be 

connected.

Air filter box (without filter)

45014AA

This additional filter box may be fitted to the MVHR system to protect 
allergy sufferers against environmental pollution with the use of finer 
filters. The filter box is installed immediately after the supply air outlet. 
Class F5 or F7 panel filters are available as the filter elements. 

Class F5 panel filter for air 
filter box

95045AA

F5 filter used in the air filter box only.

Class F7 panel filter for air 
filter box

95047AA

F7 filter used in the air filter box only.

Defrost Heater Unit

44001AA

This defrost heater unit may be fitted to the MVHR ducting system to 
pre-heat the air intake from atmosphere to prevent the build up of ice 
in the heat exchanger when the external air temperatures are below 
freezing.

6.7

Applied Energy spares available:

Description

Part Number

Terminal Cover

44301SK

Heat Exchanger

44302SK

Motor (Outgoing Air)

44303SK

Motor (Supply Air)

44304SK

G4 Filters (pack of 2)

44305SK

Control PCB

44306SK

20mm Cable Clamp

44307SK

12mm Cable Clamp

44308SK

Содержание Xcell 150 QV

Страница 1: ...1 Installation and Operating Instructions Xcell 150 QV Xcell 150 QVW Mechanical Ventilation Unit with Heat Recovery Please ensure these instructions are kept safe and accessible at all times...

Страница 2: ...ction of a voltmeter 9 6 4 Factory speed settings 9 6 5 Technical data 10 6 6 Applied Energy accessories for manual or automatic operation 10 6 7 Applied Energy spares available 10 7 Electrical Wiring...

Страница 3: ...luding children and the infirm with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the app...

Страница 4: ...l air is blown into the house and the cooled exhaust air is ducted out of the building There are numerous accessories available for controlling the MVHR see section 6 6 4 3 MVHR installation planning...

Страница 5: ...s MVHR must not be fitted in rooms or areas of the house with strong odours which could then permeate into the MVHR and contaminate the fresh air supplied from the MVHR The following criteria must als...

Страница 6: ...supplied with the MVHR can be fitted to the front or the rear and therefore the duct connections can be deter mined on site See the diagram below for the left hand duct connections Right handed instal...

Страница 7: ...be used for final connections with special care taken to avoid restrictions and other conditions which will restrict air flow 5 6 Condensate drain A condensate drain must be fitted to run to the build...

Страница 8: ...8 5 8 Installation dimensions...

Страница 9: ...ir speed 1 red pot S2 Supply air speed 2 blue pot and S 2 Exhaust air speed 2 red pot S3 Supply air speed 3 blue pot and S 3 Exhaust air speed 3 red pot Turning the potentiometer to the right increase...

Страница 10: ...e flush or surface mounted QHS sensor 96009AA The Humidistat sensor is suitable for the Xcell 150 QVW model only Note 1 When using Humidistats in conjunction with the Q3SP 3 speed switch a maximum of...

Страница 11: ...oller Xcell 150 QV Internal Terminals Green Yellow Brown Blue Bl Bn G Y 1 Phase 220 240Vac 50 60Hz N Fuse L N E N L L Bn Bl G Y 10 V O P 0V Fused Switch Spur By Others MS2 Controller 23513AW 10V O P 0...

Страница 12: ...5 open Jp6 closed Jp7 open Jp8 closed Jp9 open Jp10 open Fused Switch Spur By Others AEP Ref Xcell 150 04e a Q3SP Controller 96005AA Green Yellow Brown Blue 1 Phase 220 240 Vac 50 60Hz Fuse L N E Bn B...

Страница 13: ...p7 open Jp8 closed Jp9 open Jp10 closed Transformer G ree n Ye llow B ro wn B lue 1 Phase 220 240 Vac 50 60Hz Fuse L N E Bn Bl G Y Fused Switch Spur By Others N L AEP Ref Xcell 150 03e a QCO Controlle...

Страница 14: ...Controller 96005AA QHS Controller 96009AA QCO Controller 96003AA QHS Controller 96009AA QHS Controller 96009AA Fused Switch Spur By Others Green Yellow Brown Blue 1 Phase 220 240 Vac 50 60Hz Fuse L N...

Страница 15: ...Q3SP Controller 96005AA QHS Controller 96009AA QHS Controller 96009AA QHS Controller 96009AA QHS Controller 96009AA Fused Switch Spur By Others Green Yellow Brown Blue 1 Phase 220 240 Vac 50 60Hz Fuse...

Страница 16: ...k succession to acknowledge reset is complete Fault alarm LEDs 1 2 3 flash every second Fault alarm reset Mains voltage briefly interrupted Settings MVHR On Press plus key MVHR Off Press minus key unt...

Страница 17: ...d 3 is manually activated on the 3 speed switch the CO2 sensor is deactivated Switchpoints of the CO2 sensor 1 5 V MVHR switches from speed 2 to speed 1 900 ppm 5 0 V MVHR switches from speed 1 to spe...

Страница 18: ...an will stop the exhaust air fan will remain on When the outgoing air temperature reaches 9 C again the supply air fan comes back on automatically Settings table Option Temperature outgoing air Temper...

Страница 19: ...rrect positions in the MVHR Please note the clean side of the filter is placed next to the Heat Exchanger o Filters can be cleaned by gently knocking together to remove dust dirt Replace the Access Ha...

Страница 20: ...out by a qualified service technician Contact details for authorised servicing by Xpelair approved technicians can be found on the back of this booklet 10 1 Fault locating table FAULT MALFUNCTION CHE...

Страница 21: ...Remove the Heat Exchanger Retaining Bracket 6 Remove the Heat Exchanger carefully keeping it horizontal to avoid damaging the EPP housing 7 Remove the 4 off Terminal Cover retaining screws 8 Remove th...

Страница 22: ...d is flat against the EPP housing l Secure the new fan into place with the 3 off retaining screws m Remove the string from the new fan leads n Connect the power and control leads of the new fan to the...

Страница 23: ...23 11 Customer Notes to record details of filter recuperator cleaning etc...

Страница 24: ...24 Customer Notes continued...

Страница 25: ...25 Customer Notes continued...

Страница 26: ...26 Maintenance Log Date Action Signature Stamp...

Страница 27: ...27 This Xpelair MVHR was purchased from Supplier stamp On ________________________ date...

Страница 28: ...ited and a delivery charge made EXCLUSIONS This guarantee does not apply to the repair or replacement of Filters Accessories Isolating switches Electrical cable Fuses and or Circuit breakers or annual...

Отзывы: