Xpelair SLDC100 Скачать руководство пользователя страница 3

Preparing the fan for installation.

Remove the front cover by removing the screw from the underside of the cover and pulling off the cover from the bottom 
corners first.
Remove the electrical cover by removing the 2 screws.

Mount the fan in the hole. If working above ground floor level, safety precautions must be observed.

If installing in a wall or ceiling.
Mark the position of the backplate.

1.

Hold the backplate so that the word “TOP” marked on it is orientated correctly.

2.

Carefully insert the lip into the wall duct/ceiling.

3.

Adjust the position of the backplate until it is level.

4.

Mark on the wall/ceiling the positions of the fixing holes in the backplate.

5.

Remove the back plate from the ducting.

6.

Drill screw holes in these positions if necessary, and fit wall plugs if necessary.

Mount the backplate.

1.

If installing in a ceiling, appropriate termination ancillaries are required. Follow instructions provided.

2.

Remove knockout. Feed the mains cable through the cable entry hole in the back plate to the terminals.

3.

Insert the lip of the backplate into the wall duct/ceiling as before.

4.

Fasten the backplate to the wall/ceiling using appropriate fasteners – see Figure C.

If using screws, do not over tighten.

The fans may also be fixed to the interior of the ceiling using the clamping brackets. Tighten the screws until the fan is firmly 
fixed within the hole - see figure D.

Wire the electrical connections

.

1.

Make sure the mains supply is isolated,

2.

Wire the fan as shown in Figure E; check the fan model to diagram, feeding the cable to terminal block.

3.

Switch off the mains electrical supply and remove fuses.

4.

Connect the cable from the isolating switch to the electrical supply wiring.

For fixed wiring circuits the protective fuse for the appliance must not exceed 5A.

Setting the fan.

All Fans - Setting the Speed 

All fans have the choice of 3 speeds of extraction, which is to be set at installation:

Speed 1 – suitable for 6l/s

Speed 2 – suitable for 8l/s

Speed 3 – suitable for 15l/s

To set the required speed, set the switches to the positions shown in Figure F (these are the 3 switches marked 4, 5 and 6 
above them).

All Fans - Setting the Trickle Speed 

All fans can be set so that they provide constant trickle extraction suitable for 6l/s. 
To set the trickle speed to ON, set the switch shown in Figure F (this is the switch marked 1 above it) to the DOWN position 
(the side of the switch marked ‘ON’).
To set the trickle speed to OFF, set the switch shown in Figure F (this is the switch marked 1 above it) to the UP position 
(away from the side of the switch marked ‘ON’).  

Setting the Delay Start – SLDC100 / SLDC100PC / SLDC100T / SLDC100HT Only

These fans can be set so that there is a 2-minute time delayed start.
To set the delay start to ON, set the switch shown in Figure F (this is the switch marked 3 above it) to the DOWN position 
(the side of the switch marked ‘ON’).  
To set the delay start to OFF, set the switch shown in Figure F (this is the switch marked 3 above it) to the UP position (away 
from the side of the switch marked ‘ON’).  

SLDC100T Only

The over -run timer can be adjusted up to 30 minutes by control T.
To adjust the over-run period turn the control (T) clockwise to increase and anti-clockwise to decrease – see Figure H.

SLDC100HT Only

The pre-set humidity operation is factory set at approximately 75% Relative Humidity (RH), but can be adjusted between 
65% and 85% RH by control H.
The over -run timer can be adjusted up to 30 minutes by control T.
Turn the controls clockwise to increase RH or time and anti-clockwise to decrease – see Figure H.

Note

The switch marked 2 above it is a factory set position and should not be changed.
For the SLDC100 range this switch should be in the UP position (away from the side of the switch marked ‘150mm size’). If 
this switch is NOT in the correct position the fan will NOT achieve the required speeds.

H

G

F

Содержание SLDC100

Страница 1: ...and service Customers outside UK see international below UK Xpelair have a comprehensive range of services including Free technical advice help desk from Engineers on all aspects of ventilation Free design service quotations and site surveys Service and maintenance contracts to suit all requirements Please ask for details By telephone on Techline 44 0 844 372 7766 By fax on Techfax 44 0 844 372 77...

Страница 2: ...anual mode Use the integral pull cord switch When the fan is switched off it goes into automatic mode Light flashes when the fan is operating in manual mode External operation Use the external on off switch When the fan is switched off the fan continues to operate for the adjustable time delay then goes into automatic mode The fan can be set so that there is a 2 minute time delayed start to its op...

Страница 3: ... Speed All fans have the choice of 3 speeds of extraction which is to be set at installation Speed 1 suitable for 6l s Speed 2 suitable for 8l s Speed 3 suitable for 15l s To set the required speed set the switches to the positions shown in Figure F these are the 3 switches marked 4 5 and 6 above them All Fans Setting the Trickle Speed All fans can be set so that they provide constant trickle extr...

Страница 4: ...00 Flexible Ducting 3 XCT100 Condensation Trap Where to locate the fan Locate it as high as possible At least 110mm from the edges of the mounting surface to the centre of the hole As far away as possible from and opposite to the main source of air replacement to ensure airflow across the room e g opposite the internal doorway Near the source of steam or odours Not where ambient temperatures are l...

Отзывы: