![Xpelair Simply Silent LVCV4SR Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/xpelair/simply-silent-lvcv4sr/simply-silent-lvcv4sr_installation-and-maintenance-instructions-manual_3919297009.webp)
Fan Settings.
SPEED SETTING
The fans are factory set to bathroom speed, but have two speed settings for different applications. Select either kitchen or
bathroom speed by connecting the jumper between the centre and kitchen or bathroom speed pin on the jumper (see Figure
G)
LVCV4SR– see figures E and G.
The pre-set humidity operation is factory set at approximately 75% Relative Humidity (RH), but can be adjusted
between 65% and 85% RH by control HUM.
The over-run timer is factory set at 15 minutes but can be adjusted from 30 seconds to 30 minutes by control TIME.
The over-run timer also sets the length of time the fan runs when activated by a ‘fast’ increase in humidity.
Turn the controls clockwise to increase RH or time and anti-clockwise to decrease.
Using the fan.
The fan will run continuously at its trickle speed setting as set during the installation procedure.
Automatic mode- The fan automatically adjusts to slow changes in natural humidity levels without operating the
fan. If the humidity levels increase at a rate slower than 5% RH in 5 minutes, up to the pre-set humidity level, the
fan will not be triggered by humidity. This is to prevent nuisance triggering of the fan. If humidity levels increase
quicker than 5% RH in 5 minutes the fan will increase in speed to an interim boost speed setting. When relative
humidity drops the fan continues to operate for the adjustable time delay.When the humidity is above the pre-set
humidity level the fan will run at a higher speed until the humidity drops below the pre-set value. If humidity levels
do not drop within 5 minutes the fan will further boost to its maximum speed setting until humidity drops.
External operation- Use the external boost switch (if fitted). When the fan is switched off, the fan continues to
operate for the adjustable time delay then goes into automatic mode.
All Fans
Re-fit the front cover/baffle assembly by hooking in the top first, and then swing the cover down to clip into place.
Replacing Square Baffle with Round Baffle (Figs. F1 and F2)
Ensure fan is isolated from supply before performing this action.
1.
Remove Square Baffle/Cone assembly from Fan Front Cover by twisting anti-clockwise until all three support legs are
released from clips.
2.
Fit Round Baffle/Cone assembly by aligning clips on baffle with legs on Front Cover and rotating Baffle Clockwise
until all three clips engage and are retained on Front Cover.
Hour run meter
All fans incorporate an hour run meter that allows the installer to measure the actual running time of the fan after
installation. The meter records continuous power supply on time and displays this via an on-board red LED that always
flashes to indicate the total number of hours the supply has been on (see fig. I).
LED flash sequence to indicate hour run:
LED off for 2 seconds to indicate the start of the count, then :
0 to 2000 hours : LED on for 1 short flash (0.5s on / 0.5s off)
2000 to 3000 hours : LED on for 2 short flashes
3000 to 4000 hours : LED on for 3 short flashes
4000 to 5000 hours : LED on for 4 short flashes
5000 to 6000 hours : LED on for 5 short flashes
6000 to 7000 hours : LED on for 6 short flashes
7000 to 8000 hours : LED on for 7 short flashes
8000 to 9000 hours : LED on for 8 short flashes
9000 to 10000 hours : LED on for 9 short flashes
Each 10000 hours is indicated by 1 long flash (2.0s on / 0.5s off)