Section 4 – Installation
4.1 Requirements at the installation site
The location must be frost-free.
The room temperature should not fall below +5°C.
The Fresh air intake must be sited in an area free from unwanted odours and far enough away from the
Exhaust air outlet to prevent re-circulation.
The condensate drains must be protected from freezing.
Ensure there is at least 200mm clearance above the top surface of the unit so that the duct connections
are not restricted.
Make sure there is sufficient space around the unit for maintenance and repair work. (See dimensional
drawing).
We strongly recommend you consult a qualified specialist.
Fig. 4.1a Space needed for maintenance MVHR 180
Fig. 4.1b Space needed for maintenance MVHR 350
WARNING:
Free access to the unit and to the switch disconnecting it from the power supply must be ensured
at all times.
NOTE!
Air inlet and outlet openings and air transfer openings must not be obstructed, covered or closed
so that an unhindered airflow is ensured. Settings made by the qualified technician must not be
changed.
WARNING:
Alterations made to the unit or to the installed system as a whole as well as structural alterations
can affect safety; consult a qualified technician.
WARNING:
Using the ventilation unit together with fuel burning devices (e.g. fire places, gas stoves) is subject
to special requirements. Any applicable national as well as regional guidelines and regulations must
be observed.