Xpelair Natural Air 180 Vertical Скачать руководство пользователя страница 11

Section 6 – Control / Service menu

 

 

 

The bypass is opened

 (heat recovery is disabled) when all of the following conditions are fulfilled: 

 

 

Current date is within the set switching period (User menu /Adjust User Settings / Set up Summer Bypass) 
and 

 

Extract-air temperature is at least 1°C above the set switching temperature and 

 

Fresh-air temperature is at least 1°C below the set switching temperature 

 

The bypass is closed

 (heat recovery is enabled), when all of the following conditions are fulfilled: 

 

 

Extract-air temperature is at least 3°C below the set switching temperature and 

 

Fresh-air temperature is 1°C above Extract-air temperature 

 

6.4.2 Filter monitoring / filter message 

 

The filter is monitored on the basis of a time interval.  At the end of this interval, a message reminds the user 
of filter maintenance with a text message and flashing display. 

 

The interval is set in the User menu – Adjust User settings, and can be set within a range of 2…12 months. 
(Default setting is 6 months). The time interval can be changed at any time. 

 

Filter reset: 

 

When the “Replace Filters” message is displayed: 

 

 

Press the OK button to show “Filter replaced?”  Use the     or     buttons and 

OK

 to select “Yes” or “No”. 

 

NOTE! 

The filter interval is not reset through power failures or when the ventilation unit is switched off. 

 

6.5 Internal safety functions 

 

6.5.1 Function for safe use with open flue fuel burning devices. 

(Only to be used if permitted by relevant regulations in your country of use).

 

 

(Prevents flue gases being drawn back into the room) 

 

The ventilation unit has an integrated function for safe use with open flue fuel burning devices. 

 

This function is enabled when jumper L13 on the display circuit board is removed. 
(Indicated by an “

F

” in the standard display). 

 

When this function is enabled the flow rate of the Supply fan is automatically increased. 

 

NOTE!  

The addition of proprietary external controls, suitable for use in rooms containing an open flue 
burning devices, is strongly recommended. 

 

The unit has two configurable Flue Detection inputs for use with external controls. 

 

(See Section 6.3.2 on how to setup the Flue Detection inputs) 

 
 

WARNING:  

The higher flow rates set when this function is activated must be verified as adequate for the 
application. 

 

If the flow rates need to be changed then use “Installer Menu – Change Settings – Set Fan Speeds 
when Flue in use”. 

 

(See Section 6.3.2 on how to setup the Flue Detection inputs) 

 
 
 
 
 
 
 
 
 
 
 

30 

Section 4 – Installation

 

 

 

 

Remove the front and top cover and take the EPP unit out of the metal backplate.  

 

Offer up the backplate to the wall and mark out the mounting points, ensuring the unit is level.  

 

Secure the backplate to the wall using appropriate fixings. 

If installing on a hollow wall, suitable anti vibration fixings may be required.

  

 

If required, the unit can be fixed using left and right side fixing holes (E.g. If the unit is fixed inside a 
cupboard). 

 

Remount the unit into the backplate and secure the top and front cover.  

 

NOTE!  

Check that the unit is positioned level in order to ensure proper condensate discharge. 

 

4.3 Condensate discharge lines  

 

 

There are two condensation collection trays built into the expanded poly propylene housing (EPP) of the unit 
and two (provided) condensate collection unions must be fitted to the discharge points on the bottom side of 
the unit. 

 

 

Remove the front cover from the installed unit.  Take care to remove the umbilical connector from the 
Display PCB. 

 

Pull out the EPP cover and remove the heat exchanger using the pull strap.  

 

Remove the back-nuts from the condensate unions (provided) and then push them through the two EPP 
drain holes. 

Note: Additional leak proofing of the union may be required.

  

 

Secure the two unions to the backplate using the back nuts.  

 

Replace the heat exchanger and EPP cover.  

 

Re-fix the front cover, remembering to reattach the umbilical connector to the Display PCB.  

 

Connect drain hoses to the two unions and take to a suitable drain trap.  

 

NOTE!  

The location of the ventilation unit, as well as the condensate discharge hoses, must be frost-free!  

 

When connecting up to the drainage pipe of the building, the following points must be observed: 

 

4.3.1 Air infiltration and Infiltration of sewer gases 

 

Any air infiltration into the ventilation unit via the condensate hose must be prevented. 

 

Both condensate hoses must be looped and inclined as shown in Fig 4.3 in order to trap a loop of water and 
prevent air getting back into the unit via the hoses. 
      

(1 metre length of hose is supplied with each unit)

 

The hoses must go via a funnel or tundish to a suitable water trap as shown below. 

 

The condensate hoses from the ventilation unit must not be connected directly to the drainage pipe. 

 

 

 

 

Fig. 4.3 Condensate drain connection (schematic)

 

 
 
 
 
 

NOTE!  

Both condensate hoses MUST be made, and 

            separately run to their own drain connection. 

 

            DO NOT “common up” the two hoses.

 

 

 
 

1   Ventilation unit  
2   Looped to act as a condensate trap  
3   Condensate line with downward gradient  
4   Funnel or tundish to provide air gap  
5   Water trap to prevent bad odours entering the room  
6   Drainage line with min. 2% downward gradient 
 

11 

Содержание Natural Air 180 Vertical

Страница 1: ...Service Tel 44 0 844 372 7766 UK Technical Service Email Service request redringxpelair com A3 Part N 567140564B 40 Natural Air 180 Vertical Natural Air 180 PH Vertical Ventilation Unit With Heat Rec...

Страница 2: ...n unit is guaranteed against defects for 2 years from date of purchase Xpelair reserve the right to repair or replace the unit Keep your purchase receipt Any problems contact the address below Outside...

Страница 3: ...and any use exceeding the design limits is not permitted Any improper use can damage the unit and can cause severe hazards The unit must not be altered or modified The unit is guaranteed safe to use...

Страница 4: ...rmitted The unit is not to be used as a dehumidifier 2 2 Package contents The unit is delivered with the following package contents Ventilation unit with integrated control panel Condensate connection...

Страница 5: ...not restricted Where fitted a radial air duct system with direct pipe routes between air diffusers and supply air extract air valves Simplifies the balancing of volume flow rates and pressures Prevent...

Страница 6: ...ith WARNING Using the ventilation unit together with open flue fuel burning devices e g fireplaces gas stoves is subject to further special requirements Any applicable national as well as regional gui...

Страница 7: ...Main EPP body 11 Fan assembly 6 Top cover 12 Heat exchanger Section 3 Technical data 3 1 Specification 180 and 180 Heater Vertical Maximum volume flow rate 225 m h 62 l s Volume flow rate at speed 1 2...

Страница 8: ...2 3 2 Characteristic curves 180 Vertical Fig 3 2 Characteristic curve Natural 180 and Natural 180 PH Dotted lines represent Factory defaults 8 Section 7 Fault Finding Code Display Status Fault Cause...

Страница 9: ...ool down protection Off Switch off for frost protection of unheated rooms Exhaust air temperature 3 C switch off for frost protection unit Self induced start up when room temperature reaches 9 C E05 E...

Страница 10: ...e ventilation unit cannot be mounted on a floor Condensation drains must be fitted to the unit It is designed to be wall mounted Fig 4 2 Backplate mounted to the wall ready for remounting the unit 10...

Страница 11: ...move the front and top cover and take the EPP unit out of the metal backplate Offer up the backplate to the wall and mark out the mounting points ensuring the unit is level Secure the backplate to the...

Страница 12: ...ce menu Bypass shutter Motor Set the Bypass shutter to Open or Closed Defrost Heater When fitted the external defrost heater output can be switched On or Off Note The heater output will not switch ON...

Страница 13: ...on over the entire route To prevent condensation Any ducting that runs through unheated areas must also be fitted with thermal insulation in order to prevent heat loss 4 4 2 Vibration isolation and so...

Страница 14: ...eed Settings must be made by a qualified technician during setting up and do not normally require any further changes NOTE If the external pressure sensor continues to detect a fault and the ventilati...

Страница 15: ...flue fuel burning devices This function is enabled by removing jumper L13 on the Display PCB F is shown in the normal Display screen Set the Fan Speeds when Flue in use Use the Set Fan Speeds when Flu...

Страница 16: ...input 1 L17 External Flue Detection 1 Volt free input X2 block Volt free 2 External Volt free configurable input 2 L17 External Flue Detection 2 Volt free input X2 block Sensor 2 Internal 0 10V outpu...

Страница 17: ...ously and keep pressed for 5s Fig 6 5 User menu Refer to the User manual for a detailed description of the User menu 6 3 Installer menu Access Press the and OK buttons simultaneously and keep pressed...

Страница 18: ...hanged using the Installer menu See Section 6 3 2 Settings 18 Section 6 Control Service menu Key to Fig 6 2 1 Bypass feature is On 4 Operating status and Time 7 Program Timers are On 2 Holiday Mode is...

Страница 19: ...1 1 Standard display The standard display shows information on the current operating status of the ventilation unit Fig 6 2 Standard display 22 Section 4 Installation 4 5 7 Installation of the air qu...

Страница 20: ...or the building Set up must only be carried out when the building and rooms are ready for occupation Ensure that the rooms are free of dust eg construction material NOTE For setting up the unit and al...

Отзывы: