Section 6 – Control / Service menu
During Frost protection, the display will read Cool Down Protection.
NOTE!
In order to enable setting up, this function is not
available for 60min after energizing the ventilation unit.
NOTE!
With L13 removed: During defrosting, heat recovery is disabled and cold Fresh air flows directly into
the rooms. The installation of a Defrost heater in the Fresh air duct is recommended to prevent ice
build-up.
6.5.3 Safety cut-out function
(See also Section 4.5.8)
The Smoke Detector terminal on the Main Connector PCB is used to connect to an external smoke detector.
Connect the volt free output from the smoke detector control to the “Smoke Detector” terminals.
If an external smoke detector is not fitted then :
•
Put a shorting link across the Smoke Detector terminals on the Main Connector PCB. (See Section 4.5.1).
If the Smoke Detector terminals are open, display reads “SMOKE ALARM. UNIT IS OFF” and unit remains OFF.
•
When the Smoke Detector contacts are re-closed the display reads “SMOKE ALARM OVER. Press OK”
Unit returns to Normal and is “Off”. Select “Automatic” to start the unit again.
The ventilation unit will switch off immediately when the “Smoke Detector” terminals are opened.
Section 7 – Fault Finding
WARNING:
Repairs must only be carried out by qualified technicians.
Use only original spare parts from the manufacturer.
Filter, status and fault messages are shown on the display and control panel of the ventilation unit.
If there are any active fault messages, the display message will flash the error.
Code
Display
Status
Fault
Cause
Action
-
None (display off)
Off
No display, device not
running
No power supply
Check the power supply
-
None (display off)
Running
Faulty display
Defect of the cable to the display
circuit board or of the display
board itself
Check the cable to the display board
PCB2, replace circuit board
-
Replace Filters
Running
Filter clogged
Filter interval expired
Check / change filter, reset filter
interval
-
Cool-down
protection
Off
Switch-off for frost
protection of unheated
rooms
Exhaust-air temperature < +3°C,
switch-off for frost protection unit
Self induced start-up when room
temperature reaches > +9°C
E05
E05 External
Off
Power supply breakdown,
24V DC overload
External controllers and sensors,
incorrect wiring, short circuit or
max. number exceeded
Check wiring of external controllers
and sensors
E11
E11 Supply Start
Off
Supply fan (RHS) does not
start
No Supply fan speed for 30 s, cable
break, duct blocked or defective
Check / replace connection cable
and Supply fan
E12
E12 Extract Start
Off
Extract fan (LHS) does not
start
No Extract fan speed for 30 s,
cable break, duct blocked or
defective
Check / replace connection cable
and Extract fan
E21
E21 Fresh Air NTC Running
Internal Fresh Air sensor
Sensor or cable defective
Check / replace Fresh Air sensor
E22
E22 Supply NTC
Running
Internal Supply sensor
Sensor or cable defective
Check / replace Supply sensor
E23
E23 Extract NTC
Running
Internal Extract sensor
Sensor or cable defective
Check / replace Extract sensor
E24
E24 Exhaust NTC
Running
Internal Exhaust sensor
Sensor or cable defective
Check / replace Exhaust sensor
E25
E25 Humidistat
Running
Internal Humidistat sensor Sensor or cable defective
Check / replace Humidistat sensor
Table 7.1 Messages and faults (Continued on next page)
32
Section 3 – Technical data
Key to Characteristic curve 180
①
Speed 1 (default setting)
V
Volume flow rate (m
3
/h)
NOTE!
Each Supply & Extract speed
can be changed using
Installer Menu (see 6.3.1)
②
Speed 2 (default setting)
Δp External pressure loss (Pa)
③
Speed 3 (default setting)
3.3 Dimension drawings
Fig. 3.3 Dimensional drawing, ventilation unit
1 Exhaust air duct connection
9 Display and Control panel
2 Fresh air duct connection
10 Filter access door
3 Defrost heater, power outlet
11 Front cover
4 Boost heater, power outlet
12 Condensate connection point A
5 Supply air duct connection
13 Condensate connection point B
6 Voltage supply feed
14 Bottom panel
7 External sensor connections
15 Side panel (2 off) c/w 4 side mounting holes
8 Extract air duct connection
16 Back panel c/w 4 back mounting holes
9