background image

 

Installation  

 

The installation should minimise resistance and prevent any leakage in the ducting. Where possible the 
use of flexible ducting should be avoided. If an extract spigot is not used it should be closed with a cover.  
If installing in a position where condensation is likely to run back towards the fan, you will need a 
suitable condensation trap. 
Position of air intake: 

 

As far as possible from and opposite to the main source of air replacement to ensure airflow 
across the room (e.g. Opposite an internal doorway). 

 

Near the source of steam or odours. 

 

Not where ambient temperatures are likely to exceed 50ºC, or above a cooker hob or eye level 
grille. 

 

If installing in a room containing a fuel burning device, it is the installer’s responsibility to 
ensure that there is enough replacement air to prevent fumes being drawn down the flue when 
the fan is operating up to maximum extract. Refer to Building Regulations for specific 
requirements. 

 

Exhaust air must not be discharged into a flue used foe exhausting fumes from appliances 
supplied with energy other than electric. Requirements of all authorities concerned must be 
observed for exhaust air discharge. 

 

The inlet grilles should be situated at least 0.5m distance from the discharge outlet of a flued 
heating or cooking appliance. 

Position of the air outlet: 

 

At least 0.5m away from open door or window, or the inlet of another ventilation device. 

The fan unit must always be firmly fixed.  
This can be done by either of the methods below: 

 

Using woodscrews fixed through the corner of the ventilator box.  

 

Using threaded bolts in the notched holes.  

 

Electrical  

 

The Xvent 340 and Xvent 340DC can be wired to run at speed 1, 2 or 3 or by use of a 3-speed switch, 
which gives speed choices to the user. The Xvent 340DCRF is to be wired to run at 3 speeds by use of the 
RF wireless control system. See section on remote control. For wiring of the ventilation unit see wiring 
instructions.  

 

Maintenance  

 

This fan unit requires little maintenance.  
Every 4-5 years it is advised to disassemble the unit, remove the motor and impeller assembly and clean 
the impeller using soapy water (making sure that water does not get into the motor)  

 

CE-conformity  

 

This unit meets all relevant CE standards.  

 

Removing the cover  

 

Insert a screwdriver in one of the 4 openings in the slanting corners of the box.  
Turn the screwdriver so that the corner piece unlocks and loosens the cover.  
It may be necessary to unlock more than one corner.  

 

Removing the motor and impeller assembly  

 

Remove the motor and impeller assembly by using the 3 click connections fixed to the casing.  
Insert a screwdriver into

 

one of the grooves and turn it until the section becomes free.  

When all 3 positions are loosened the motor plate can be removed from the casing.  
Reassembly  
Place the ventilator unit in the correct position and click the cover back in place.  
 

Содержание 340

Страница 1: ...eed position as a background position if the house is not fully occupied In a smaller dwelling or flat the low speed position could be the normal running position with the middle position as a boost The fan is designed to run continuously 24 hours a day It is fitted with an energy efficient electric motor Maintenance In normal running the design of the fan attracts very little dirt It may be advis...

Страница 2: ...5m away from open door or window or the inlet of another ventilation device The fan unit must always be firmly fixed This can be done by either of the methods below Using woodscrews fixed through the corner of the ventilator box Using threaded bolts in the notched holes Electrical The Xvent 340 and Xvent 340DC can be wired to run at speed 1 2 or 3 or by use of a 3 speed switch which gives speed ch...

Страница 3: ...llations and wiring must conform to current IEE Regulations UK local or appropriate regulations other countries A means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules 1 Switch off the mains electrical supply and remove all fuses before commencing wiring 2 Wire the fan as shown below 3 Connect the cable from the isolating switch to the electrical supp...

Страница 4: ...er PROGRAMMING Using a fine screwdriver briefly 1 6 sec press the flush programming key situated on the receiver on the Xvent unit A light signal starts flashing flashing 1 sec Program all RF emitters that have to interwork with the receiver one by one The correct reception of an address is acknowledged by a long light signal 4sec Up to 32 emitters can be programmed per receiver When this maximum ...

Страница 5: ...he Xvent 340 is guaranteed against defects for 3 years from the date of purchase UK The Xvent 340DC Xvent 340DCRF is guaranteed against defects for 5 years from the date of purchase Please keep your purchase receipt If you have any problems contact Xpelair s Head Office at the address shown below Customers outside UK see international below UK Xpelair have a comprehensive range of services includi...

Отзывы: