- 6 -

Installa

tion P

repar

ation

DUCT FITTINGS:

This Hood Must Use an

6" Round Duct. It Can

Transition to 3-1/4" x

10" or 3-1/4" x 12" Duct.

Use  this  chart  to  compu-

te  maximum  permissible 

lengths  for  duct  runs  to 

outdoors.

NOTE:

 

Do not exceed maxi-

mum permissible equivalent 

lengths!

Maximum  duct  length: 

100  feet  for  range  ho-

ods.
Flexible ducting:

If  flexible  metal  ducting 

is used, all the equivalent 

feet  values  in  the  table 

should  be  doubled. The 

flexible metal duct should 

be  straight  and  smooth 

and extended as much as 

possible.
DO NOT use flexible plastic 

ducting.

NOTE:

 

Any home ventilation 

system, such as a ventilation 

hood,  may  interrupt  the 

proper flow of combustion 

air  and  exhaust  required 

by fireplaces, gas furnaces, 

gas water heaters and other 

naturally vented systems. To 

minimize the chance of in-

terruption of such naturally 

vented systems, follow the 

heating equipment manu-

facturer’s  guidelines  and 

safety  standards  such  as 

those published by NFPA.

Duct 

Piece:

Dimensions:

Equivalent 

Number 

Length*:

Quantity

Used:

Total

Equivalent

Length:

Round, straight 1 ft. (per foot 

lenhgth)

3-1/4" x 10" 

straight

1 ft. (per foot 

lenhgth)

90° elbow

12 ft.

45° elbow

7 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

14 ft.

10 ft.

3-1/4" x 10"

3-1/4" x 12"

45° elbow

8 ft.

6 ft.

3-1/4" x 10"

3-1/4" x 12"

90° elbow

33 ft.

24 ft.

6" round to 

rectangular

2 ft.

Rectangular to 

8" round

2 ft.

3-1/4" x 10"

3-1/4" x 12"

6" round to 

rectangular 

transition 90° 

elbow

4 ft.

4 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular to 

6" transition 

90° elbow

4 ft.

4 ft.

Round wall 

cap with 

dramper

24 ft.

3-1/4" x 10"

3-1/4" x 12"

Rectangular 

wall cap with 

dramper

24 ft.

18 ft.

Round roof 

cap

33 ft.

*Actual  length  of  straight  duct  plus  duct 

fitting  equivalent.  Equivalent  length  of  duct 

pieces  reflect  requirements  for  good  venting 

performance with any ventilation hood.

Total Duct Run =

Содержание XOM36G

Страница 1: ...A Manual de utilizaci n USA F E XOM30G XOM36G NEED HELP Call our ventilation experts toll free al 800 966 8300 AVEZ VOUS BESOIN D AIDE Contactez nos experts au num ro gratuit 800 966 8300 NECESITA AYU...

Страница 2: ...ginal purchaser for products purchased for ordinary home use in North America Should you require service for your XO product call a product service specialist at 800 966 8300 Improper Installation Ser...

Страница 3: ...and vapors CAUTION To avoid motor bearing damage and noisy and or unbalanced impellers keep drywall spray construction dust etc off power unit CAUTION Please read specification label on product for f...

Страница 4: ...nguisher ONLY if 1 You know you have a Class ABC extinguisher and you already know how to operate it 2 The fire is small and contained in the area where it started 3 The fire department is being calle...

Страница 5: ...s after a prolonged use of the appliance C No food must be cooked flamb underneath the hood D The use of an unprotected flame is dangerous for the filters and could cause fires E Watch constantly the...

Страница 6: ...erruption of such naturally vented systems follow the heating equipment manu facturer s guidelines and safety standards such as those published by NFPA Duct Piece Dimensions Equivalent Number Length Q...

Страница 7: ...e or Duct Tape INSTALL THE DUCTWORK NOTE To reduce the risk of fire use only metal ductwork 1 Decide where the ductwork will run between the hood and the outside 2 A straight short duct run will allow...

Страница 8: ...8 Hood Specifications Front of hood Side of hood Top of hood Mounting height and clearance Product dimensions and clearance XOM30G XOM36G...

Страница 9: ...appliance has been adjusted definitely fix the hood using the screws A Fig 2 For the vari ous installations use screws and screw anchors suited to the type of wall e g reinforced concrete plasterboar...

Страница 10: ...t be 2 wire with ground If the electrical supply does not meet the above requirements call a licensed electrician before proceeding Route house wiring as close to the installation location as possible...

Страница 11: ...as indicated in Fig 3 Before installing the appliance fix the electrical box as indicated in Fig 3 Fig 3B Lift the electrical plant box Fig 3D Position the electrical box so it is in line with the hol...

Страница 12: ...ing listed conduit fittings Carry out the power supplly connection in accordance with the national electric code ANSI NFPA 70 1999 5 Insert the wires into the box then close the box cover securing it...

Страница 13: ...bracket of the upper flue Fig 7 Then fix it to the ceiling using the screws A Fig 7 in such a way that it is in line with your hood and respecting the distance from the ceiling indicated in Fig 6 Conn...

Страница 14: ...G Remove the two flues F G and place them on a flat surface Carbon filter kit XORFK01 The kit includes an air diverter A 2 screws and 2 expan sions plugs B and 2 rectangular filters C Fig 2 Make a ma...

Страница 15: ...r A and drill two holes as shown in the figure hole diameter 1 4 inches Once the two holes have been drilled fasten the air diverter A to the bracket H Fig 5 Fasten the air diverter permanently to the...

Страница 16: ...e F to the bracket and fasten it using the 2 screws E Fig 8 Remove the aluminum panels by pulling the lever 1 out and pushing downwards 2 Fig 9 The charcoal fi lters C must be fit ted in the ducting u...

Страница 17: ...and the LED of key F remains switched on with a fixed light until the motor starts up again at the first speed after fifty minutes and keys F and C start to flash again for ten minutes and so on By p...

Страница 18: ...which is released back into the room The filters are not washable or re usable and must be replaced at least once every four months The active carbon filter saturation level depends on the frequency w...

Страница 19: ...e causing rust DO NOT allow salt solutions disinfectants bleaches or cleaning compounds to remain in contact with stainless steel for extended periods Many of these compounds contain chemicals with ma...

Страница 20: ...sity it can be replaced only by special ized personnel Replacing halogen light bulbs To replace the halogen light bulbs B remove the glass panel C using a lever action on the relevant cracks Replace t...

Страница 21: ...21 XOM30G XOM36G...

Страница 22: ...22 OPTIONS AND ACCESSORIES Model XORFK01 Ductless Recirculating Filter Kit Model XOEDCM Duct Cover Extension This accessory is available for installation with ceiling heights above 9ft to 10 ft...

Страница 23: ...t 2 B 1 8 x 6 8 Screws for attaching the decorative flue to the mounting bracket 6 Duct bracket Aluminum filter 2 piece decorative duct cover dimension shown for reference only INSTALLATION PREPARATIO...

Страница 24: ...cleaning Mounting Height from cooking surface 27 32 Duct Options and Electrical Requirements 6 inch duct required Ductless Option for applications where no ducting in available AC 120v 60Hz 4 35amp O...

Отзывы: