![Xmart SUPRA 501 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/xmart/supra-501/supra-501_user-manual_3542766002.webp)
USER MANUAL - SUPRA 501/700/901
www.xmart-ups.com
VER. 170313-AP_VE
3
2.
SAFETY & QUALITY STANDARDS
SAFETY - LOW VOLTAGE DIRECTIVE (2014/35/EU)
UPS Part 1-1: General & Safety UPS in accessible areas
IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY - EMC DIRECTIVE ( 2014/30/EU)
UPS, Part 2, Electromagnetic Compatibility:
IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals:
IEC/EN 61000-2-2
Electrostatic discharge immunity Test:
IEC/EN 61000-4-2
(Air: Level 3, Contact: Level 2)
Radiated radio Frequency immunity:
IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity:
IEC/EN 61000-4-4 (Level 3)
Surge immunity:
IEC/EN 61000-4-5
(L-L: Level 2, L-G: Level 3)
UPS Part 3: Methods of operation, specifications and test requirement
IEC/EN 62040-3
IT Equipments. SAFETY. Part 1: General Requirements
IEC/EN 60950-1
IP PROTECTION
IP20 (static)
QUALITY MANAGEMENT: ISO 9001 : 2000
Manufactured under:
ISO 9001
ENVIRONMENTAL MANAGEMENT: ISO 14001 : 2004
Manufactured under:
ISO 14001
Any modification made by user or operator may affect compliance of the safety and performance certifications listed above.
UPS manufacturer is not responsible of any modification made on the product or its accessories after it is manufactured.
This product is designed to operate in domestic and commercial environment. CE standards apply for 230V models.
This is a C2 category product. In residential environment, this product may cause radio interference, in this case the user may
require to take additional measures.
3.
BATTERY MAINTENANCE
Batteries capacity, in general (of all kinds), decreases with time and use.
Our products contain high quality batteries only.
Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under
25ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and
other adverse operation condition.
Batteries life expectancy may be also affected by other operation conditions such as electrical service
quality as well as number and kind of equipments connected to UPS
Batteries should be periodically tested to check capacity and assure and appropriate back up.
* To enlarge batteries life expectancy it is recommendable to fully discharge UPS once every 3 months
* During long UPS storage recharge batteries according to following table:
STORAGE TEMPERATURE
FREQUENCY
RECHARGING TIME
-25°C a +30°C
Every 4 months
4 h
+30°C a +45°C
Every 2 months
4
h
USER MANUAL - SUPRA 501/700/901
www.xmart-ups.com
VER. 170313-AP_VE
4
4.
UPS DESCRIPTION
This kind of equipment is known as UPS (Uninterruptible Power Supply). It has 2 main functions: give electrical
protection against surges, spikes and some other dangerous failures of electrical main system and also
provides electrical backup based on internal batteries. In that way products you connect to your UPS will be
protected and will receive electrical energy even during failures of main electrical AC system.
This UPS is designed to satisfy all requirements of Personal Computers (PCs). It includes internal voltage
regulator to stabilize input AC variations without using internal batteries. Only in presence of important input
failures UPS will use internal batteries to provide energy in outlet sockets. In this way batteries life expectancy is
longer.
SUPRA 501/701/901 series
: It is an interactive UPS with step-wave output. It includes surge protection in all
AC outlets. RJ45 & RJ11 sockets also include surge protection for the phone line of the router.
1.- Output sockets
4.- USB (optional in 120V models)
2.- Input AC
5.- RJ45 / RJ11 surge protected sockets
3.- Input breaker
UPS will provide backup energy in its outlets when main AC input fails. Runtime will depend on some different
factors:
Battery charging level.
Battery capacity according to the use given and lifetime.
Load consumption connected to UPS outlets. Higher the output load shorter the runtime.
Under normal condition, when UPS is ON and connected to AC source, UPS will keep batteries fully charged.
This UPS is not compatible with power plants and generators. Do not connect this UPS to outlets
supplied by power plants / generators.