INDEX
USER MANUAL - OPTIMA T09 1K/1.5K/2K/3K
www.xmart-ups.com
VER.170502-GA2 (ENG)
14
09
PROG-OUTPUT: ENABLE / DISABLE PROGRAMMABLE OUTPUTS:
Enables/disables programable output (check function 11)
ENA : ENABLE
DIS : DISABLE
Factory set: DIS
10
PROG-OUTPUT: MAXIMUM RUNTIME FOR PROGRAMMABLE OUTLETS:
0-999: Time in minutes for programable outlets in Battery mode (if function 10 is
enable).
Factory set: 999 min.
This setting does not affect runtime for standard UPS outlets.
11
MAXIMUM RUNTIME:
This function sets maximum time in Battery mode for the UPS.
000 a 999: Max. Time in minutes.
DIS: Disable. Runtime will be limited by Battery charge level only.
Set values with keys:
&
12
BATTERY CAPACITY IN AH:
This function must be adjusted only if external batteries are connected to the UPS.
Adjusted value must describe total AH (in external) connected to UPS.
For example, if UPS has internal bank of 9AH and other external 9AH battery bank is
connected, the value to be set is 18AH.
0-999: value can be set 7AH to 999AH
13
BATTERY CHARGER CURRENT:
Sets recharging current in Amps (1, 2, 4, 6 or 8ª)
Models with supercharger: 8A
Standard chargers: 4A max.
14
BOOSTING CHARGING VOLTAGE:
** NO MODIFICATIONS RECOMMENDED
–
ONLY FOR TECHNICIANS **
Charging voltage can be increased
Adjustable Voltage: 2.25V per cell up to 2.40V per cell
6 cells per battery
Factory set: 2.36V/cell
2.36*6= 14.16V per battery
15
FLOATING RECHARGING VOLTAGE
** NO MODIFICATIONS RECOMMENDED
–
ONLY FOR TECHNICIANS **
2.20V per cell up to 2.33V per cell. (6 cells per Battery)
Factory set: 2.28V/cell
2.28*6= 13.68V per battery