Installation 
 
Installing the Display Unit (G1BR-B01-D/G1CR-B01-D or G2BS-B01-D) 
 
The Display Unit should be located at the instrument panel, so that the visible and audible 
indicators may be easily observed.   
 
Drill a 2-

1/16” hole to accommodate 

the G1BR-B01-D/G1CR-B01-D Display Unit. 

Drill a 2-

1/8” hole to accommodate the G2BS

-B01-D Display Unit. 

 
Insert Display Unit into hole and secure with the provided threaded mounting nut.  A Trim Ring is 
available if needed. 
 

NOTE 

DO NOT MAKE ELECTRICAL CONNECTIONS AT THIS TIME.  THEY WILL BE ADDRESSED IN A LATER 
SECTION. 
 
Routing Sensor Cable(s) (FS-

X01 CABLE XX’)

 

 
A 20 FT Sensor Cable is provided for each Gasoline Fume Sensor.  The Sensor Cables should be 
routed starting at the Display Unit, then to the pre-determined location of the Gasoline Fume 
Sensor.  Connect to the Display Unit using the attached quick-disconnect connectors.  Take care 
not to pinch, break, or cut the Sensor Cable or put too much stress on the connectors while 
routing the cable.  Secure the Sensor Cable with the appropriate hardware for the application.   
 

NOTE 

DO NOT CUT EXTENSION CABLE FOR ANY PURPOSE.  DOING SO VOIDS THE PRODUCTS 
WARRANTY.  LONGER CABLES ARE AVAILABLE FROM 20 FT TO 100 FT.   
 
Installing Gasoline Fume Sensor(s) (FS-T01) 
 
The 

Gasoline Fume Sensor should be located in the Bilge, just above the “Slosh Line”.  A good rule 

of thumb is to install no lower than the height of the starter solenoid.  Avoid locating sensors near 
manifold or exhaust systems, as high heat may damage the sensor.   

 

Use the appropriate #8 mounting hardware to mount the Gasoline Fume Sensor in the desired 
location.  The rubber gasket should be installed between the sensor and the mounting surface.   

 

Connect to the Extension Cable using the attached quick-disconnect connectors.   

 
 
 
 
 

 

Содержание G-1BB

Страница 1: ...l 24V Solenoid G 1CB R Chrome Round Blower Control 12V Solenoid G 1CB 24 R Chrome Round Blower Control 24V Solenoid Dual Channel System G 2BB R Black Square Blower Control 12V Solenoid G 2BB 24 R Black Square Blower Control 24V Solenoid Owner s Manual Installation Instructions Read and comply with all instructions warnings and limitations before installing servicing or removing this device ...

Страница 2: ...s 4 Installation 6 Installing the Display Unit G1BR B01 D G1CR B01 D or G2BS B01 D 6 Routing Sensor Cable s FS X01 CABLE XX 6 Installing Gasoline Fume Sensor s FS T01 6 Electrical Connections G1BR B01 D G1CR B01 D or G2BS B01 D 7 Testing the System Operation 7 Testing the Gasoline Fume Sensors 7 Maintenance 8 In the Event of an Alarm 8 Repairing Xintex Gasoline Detection Components 8 Returning Xin...

Страница 3: ...stem Specifications G 1BB R G 1CB R Operating Voltage 9 30V DC Nominal Current Draw 55mA 12V DC Maximum Current Draw 95mA 9V DC Maximum Blower Output Current 2A Operating Temperature 40 F 40 C to 185 F 85 C Alarm Horn 68 dB System Specifications G 1BB 24 R G 1CB 24 R Operating Voltage 18 30V DC Nominal Current Draw 34mA 24V DC Maximum Current Draw 46mA 18V DC Maximum Blower Output Current 2A Opera...

Страница 4: ...l The Red LED located at the bottom indicates a fume buildup of 20 of the LEL Lower Explosive Limit which is considered an alarm The Blower status LED and alarm horn will actuate when the Red LED is illuminated Whenever the Blower status LED is illuminated the Blower is active The alarm status will continue as long as the fume level remains at an elevated level The alarm horn may be silenced by pr...

Страница 5: ...r Switch YELLOW Switching Ground 2A Fuse Included Positive voltage from Blower Circuit Breaker MB30RLY 30 85 87 86 G1BR B01 D G1CR B01 D FS X01 CABLE XX FS T01 RED Power 1 0 Amp Fuse from Circuit Breaker BLACK Ground Blower Ground YELLOW Switching Ground 2A Fuse Included Positive voltage from Blower Circuit Breaker MB30RLY 30 85 87 86 Blower Switch ...

Страница 6: ... of the Gasoline Fume Sensor Connect to the Display Unit using the attached quick disconnect connectors Take care not to pinch break or cut the Sensor Cable or put too much stress on the connectors while routing the cable Secure the Sensor Cable with the appropriate hardware for the application NOTE DO NOT CUT EXTENSION CABLE FOR ANY PURPOSE DOING SO VOIDS THE PRODUCTS WARRANTY LONGER CABLES ARE A...

Страница 7: ...me Detectors can be tested by pressing the Check Reset button on the face of the Display Unit The Display Unit will cycle through the LEDs and the alarm horn will activate while the LEDs cycle Unplug the Gasoline Fume Sensor from each channel of the Detection System one at a time The Yellow Fault LED should illuminate If the Yellow LED does not illuminate remove Display Unit and return direct to m...

Страница 8: ...y and make any necessary repairs Repairing Xintex Gasoline Fume Detection Components Xintex Gasoline Fume Detection Components are not field serviceable Components must be returned to the factory for any repairs Returning Xintex Gasoline Detection Components No product may be returned for credit or repair without a written Returned Material Authorization RMA form Purchaser must call or email Fireb...

Страница 9: ...ment of Fireboy Xintex LLC does not assume the costs of removal and or installation of the product or any other incidental costs of removal and or installation of the product or any other incidental costs which may arise as a result of any defect in material or workmanship and e upon discovery of defect Buyer shall immediately cease use of and notify Fireboy Xintex LLC Any warranty implied by law ...

Отзывы: