Installation requirements:
1. TH has four ferric mounting racks when out of factory, there are two square holes on the up, down
side of TH, use mounting rack to fix the TH with control cabinet.
In order to avoid TH temperature too high after long time working, please keep 10cm space on the
up/down and 5cm on the left/right side of the TH when installing.
2. Installation steps:
a) Refer to the dimension in the former chapter to open a rectangle mounting hole in the control
cabinet
b) Add airproof circles in the airproof slot when installing
c) Insert the bottom of TH into the mounting hole of control cabinet
d) Insert the install rack into the fix hole of TH then tighten the screw
e) Connect TH and PLC with communication cable
Note:
The communication cable can be offered by the supplier or made by user according to the connection
map, input +24V DC power to start working
3. Environment
Please use TH series touch screen indoors.
Do not use TH in below environments:
Inflammable gas, steam, dust, fast vary temperature, high humidity (it may cause moisture inside TH).
4. Power supply requirements:
TH series touch screen use DC +24V power supply only. The permitted voltage range is 20V~28V.
The connection is as below:
Besides, if connect high voltage or AC power supply with TH, the TH may be damaged and cause
electric shock to human body.
Note:
If use the DC +24V output of PLC to drive the TH, make sure the PLC has enough current to drive the
TH.
Fixed bracket
Install panel
3-3 Installation and using environment
+24V 0 V