background image

Combustion Air Filter

This heater is supplied with an integral combustion air

filter. This filter will reduce the amount of particulates

that  pass  through  the  combustion  system  and  heat

exchanger but will not protect against chemical inside

air contamination (See Appendix). The filter must be

checked periodically to verify that adequate combus-

tion  air  is  being  supplied  to  the  heater.  See  the

Maintenance section of this manual for information on

checking the filter and establishing service intervals.

Direct Vent

If outside air is drawn through the intake pipe directly

to the unit for combustion:

1. Install the combustion air ducting kit.

2. Install  combustion  air  direct  vent  in  accordance

with Fig. 24 (horizontal) or Fig. 26 (vertical) of this

manual.

3. Ventilation of the space occupied by the heater(s)

is recommended and can be provided by an open-

ing(s)  for  ventilation  air  at  the  highest  practical

point communicating with the outdoors.  The total

cross-sectional area should be at least 1 in² of free

area per 20,000 BTUH (111 mm² per kW) of total

input rating of all equipment in the room when the

opening  is  communicating  directly  with  the  out-

doors  or  through  vertical  duct(s).    The  total

cross-sectional area should be at least 1 in² of free

area per 10,000 BTUH (222 mm² per kW) of total

input rating of all equipment in the room when the

opening  is  communicating  with  the  outdoors

through horizontal duct(s).  Damage to the equip-

ment due to inadequate ventilation of the space is

not a warrantable failure.

4. In cold climates, and to mitigate potential freeze-

up, Raypak highly recommends the installation of

a  motorized  sealed  damper  on  the  air  intake  to

prevent  the  circulation  of  cold  air  through  the

heater during the non-operating hours.

TruSeal™ Combustion Air

In addition to the 4 previous steps, combustion air may

be ducted directly to the heater by using PVC, CPVC

or sealed single-wall galvanized ducting. The duct will

attach directly to the air collar located on the rear of the

heater when the combustion air ducting kit is installed,

using three or four sheet metal screws (not supplied)

equally  positioned  around  the  circumference  of  the

duct. The screws and duct connection point must be

sealed with RTV (not supplied). TruSeal is generally

used when damaging contaminants are present in the

mechanical room. All ducting must be self-supported. 

Conventional Combustion Air

Supply

U.S. Installations

All Air from Inside the Building

The confined space shall be provided with 

TWO

per-

manent  openings  communicating  directly  with  an

additional room(s) of sufficient volume so that the com-

bined  volume  of  all  spaces  meets  the  criteria  for  a

room large in comparison (NFGC). The total input of all

gas  utilization  equipment  installed  in  the  combined

space shall be considered in making this determina-

tion. 

Each opening

shall have a minimum free area of

1 in.

per 1,000 BTUH (2,225 mm

2

per kW) of the total

input rating of all gas utilization equipment in the con-

fined space, but not less than 100 in.

2

(645 cm

2

). One

opening shall commence within 12 in. (305 mm) of the

top,  and  one  opening  shall  commence  within  12  in.

(305  mm)  of  the  bottom  of  the  enclosure. The  mini-

mum dimension   of air openings shall be not less than

3 in. (76 mm) in any direction.

All Air from Outdoors

The confined space shall communicate with the out-

doors in accordance with one of the methods below.

The minimum dimension of air openings shall not be

less than 3 in. (76 mm) in any direction. Where ducts

are  used,  they  shall  be  of  the  same  cross-sectional

area as the net free area of the openings to which they

connect.

1.

Two  permanent  openings

,  one  commencing

within 12 in. (305 mm) of the top, and one com-

mencing within 12 in. (305 mm) of the bottom of

the  enclosure,  shall  be  provided.  The  openings

shall  communicate  directly,  or  by  ducts,  with  the

outdoors or spaces (crawl or attic) that freely com-

municate with the outdoors.

CAUTION:

Use  TruSeal  combustion  air  if

damaging  airborne  contaminants  are  or  may  be

present in the boiler area. See the Appendix of this

manual regarding air contamination.

NOTE:

To ensure proper cooling and ventilation of

components,  do  not  block  any  air  openings  in  the

cabinet

11

Содержание 300A

Страница 1: ...vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any applia...

Страница 2: ...ge 17 Table J on page 18 Table L on page 19 Fig 22 on page 28 Termination on page 29 Fig 23 on page 30 Wiring Diagram on page 44 Table Y on page 47 Additions Table G on page 13 Warning on page 29 Ther...

Страница 3: ...ons 21 Venting 25 Venting Installation Tips 28 Venting Configurations 28 Condensate Management 33 Outdoor Installation 34 Controls 34 Operating Instructions 37 WIRING DIAGRAM 44 START UP 45 Pre Start...

Страница 4: ...WARNING CALIFORNIA PROPOSITION 65 This product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm WARNING Risk of electrical shock More than o...

Страница 5: ...k s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel The model number has...

Страница 6: ...ig 2 Component Locations Top Fig 3 Component Locations Rear Model No MBTUH Input Water conn NPT Gas conn NPT Vent Size inches Max Min N P Flue Intake 300A 300 60 1 1 2 3 4 3 4 4 4 400A 399 80 2 1 1 4...

Страница 7: ...water for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury Contact a licensed plumber or the...

Страница 8: ...be located at least 18 in above the floor In addition the heater shall be installed such that the gas ignition system components are protected from water dripping spraying rain etc during appliance op...

Страница 9: ...ll local codes NOTE Use of this boiler in construction areas where fine particulate matter such as concrete or dry wall dust is present may result in damage to the boiler that is not covered by the wa...

Страница 10: ...ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved...

Страница 11: ...of the heater when the combustion air ducting kit is installed using three or four sheet metal screws not supplied equally positioned around the circumference of the duct The screws and duct connectio...

Страница 12: ...be drawn from the air outside of the building the mechanical equip ment room must communicate directly with the outdoors Canadian Installations 14 000 BTUH 160 mm2 per kW in excess of 1 million BTUH T...

Страница 13: ...valve Carefully fill the rest of the system making sure to eliminate any entrapped air by using high point vents Close feed valve Test at standard operating pressure for at least 24 hours 2 Make sure...

Страница 14: ...70 34 19 H7 850A 80 40 53 17 46 12 41 10 39 80 40 20 Fig 6 Air Separation Expansion Tank Air Separation Expansion Tank All heaters should be equipped with a properly sized expansion tank and air separ...

Страница 15: ...or heat is present The Boiler Pump P1 runs during any call for heat The Indirect DHW Pump P3 runs during an indirect call for heat with no off delay The Boiler Pump P1 and System Pump P2 delay off as...

Страница 16: ...whenever the system is enabled The Boiler Pump is delayed off after the Tank Target temperature is achieved and as user defined in the ADJUST menu Domestic Hot Water When designing the water piping sy...

Страница 17: ...21 9 WH7 400A 1630 1 2 39 21 0 19 4 WH7 500A 1630 1 2 48 20 7 19 8 WH7 700A 1634 1 69 36 0 19 3 WH7 850A 1634 1 69 36 0 23 4 WARNING Plumbing between the heater and tank in excess of 75 equivalent fee...

Страница 18: ...e heater gas controls When connecting additional gas utilization equipment to the gas piping system the existing piping must be checked to determine if it has adequate capacity for the combined load T...

Страница 19: ...6 220 310 795 850A 25 55 55 125 175 450 for pilot duty only XFyre heaters may power up to 2 pumps directly Install a circuit breaker sized sufficient ly for both the heater and the pump s An indirect...

Страница 20: ...dicated circuit breaker should be provided and sized for the heater and all pumps powered through the heater 2 Turn off all power to the heater Verify that power has been turned off by testing with a...

Страница 21: ...LARM CONTROL SENSOR WIRING HIGH VOLTAGE POWER AND PUMP WIRING LOCATION RATING PLATE SUGGESTED ROUTING OF SENSOR CONTROL WIRING Fig 14 Rear Wiring Location Fig 16 XFyre Single Heater Control PLATFORM I...

Страница 22: ...to ensure nei ther of these terminals becomes connected to ground Wiring the Optional 0 10 Volt Building Control Signal 1 A signal from an energy management system may be connected to the XFyre boiler...

Страница 23: ...voltage 120 volt or greater wiring Raypak recommends that the total maxi mum length of each set of communication bus cables not exceed 200 feet 3 Route the FT_BUS wires from the front along the top ra...

Страница 24: ...Fig 16 This connection must be pro vided through dry contacts closure NOTE This dry contacts closure can come from a room thermostat or a remote relay No power of any kind should be applied to either...

Страница 25: ...nsate The vent adapter kit supplied by Raypak includes a higher temperature rated vent limit Vent installation shall be in accordance with Part 7 Venting of Equipment of the NFGC ANSI Z223 1 NFPA 54 S...

Страница 26: ...area where condensate or vapor could create a nuisance or hazard or could be detrimen tal to the operation of regulators relief valves or other equipment 6 Locate and guard vent termination to preven...

Страница 27: ...tion Code A vent shall not terminate 1 Directly above a paved sidewalk or driveway which is located between two single family dwell ings and serves both dwellings 2 Less than 7 ft 2 13 m above a paved...

Страница 28: ...ract 10 ft per elbow Max 4 elbows Only Centrotherm polypropylene is approved for the XFyre product 8 OR LESS Fig 22 Vertical Venting Model No Certified Vent Material Vent and Intake Air Vent Size in V...

Страница 29: ...moval of an existing boiler the follow ing steps shall be followed with each appliance remaining connected to the common venting system placed in operation while the other appliances remain ing connec...

Страница 30: ...Category IV Note Heaters rotated to show venting connections An extractor is required for this configuration Fig 24 Horizontal Through the Wall Venting Refer to Table F and local codes Fig 25 Horizon...

Страница 31: ...mum of 4 elbows each on the air intake and vent The vent cap is not considered in the overall length of the venting system The vent must be installed to prevent flue gas leakage Care must be taken dur...

Страница 32: ...h per foot of hori zontal run to the vent terminal Termination The vent cap MUST be installed on the exterior of the building The vent cap cannot be installed in a well or below grade The vent cap mus...

Страница 33: ...ge to the drainage system and to meet local code requirements Vent pipe condensate drains are also required for installation of the XFyre Follow vent manufacturer instructions for location of condensa...

Страница 34: ...ventilation air Keep area clear and free of combustible and flammable materials 3 Do not locate adjacent to any window door walk way or gravity air intake The vent must be located a minimum of 4 ft ho...

Страница 35: ...perature device as standard and it may have an additional optional adjustable manual reset high temperature device Standard The fixed setting manual reset high limit is built into the PIM it utilizes...

Страница 36: ...evel drops below the level of the sensing probe A 5 second time delay pre vents premature lockout due to temporary conditions such as power fluctuations or air pockets Fig 31 Flow Switch Fig 32 Flue T...

Страница 37: ...to prevent the operation of the boiler when a significant amount of air flow is blocked at the vent The switch is located at the left rear of the unit Fig 35 Blocked Vent Switch 37 Thermal Fuse The he...

Страница 38: ...ary follow Adjusting The XFyre Setpoint in this section 3 On the initial start up of units with gas pressure switches the control user interface will display GAS PRESS This is a low gas pressure switc...

Страница 39: ...ature 192 F TARGET MIN H 1 2 3 OFF 50 F to 190 F Minimum target boiler temperature 50 F TARGET DIFF H 1 2 3 2 F to 42 F Differential for target boiler temperature 10 F DHW SENSOR H 1 2 3 OFF ON Select...

Страница 40: ...High Limit Offset OPERATOR All Operator Limit Potentiometer PIM AUTO DIFF H 1 2 3 Current auto differential PUMP PREPt All Duration of pump prepurge BLOW PREPt All Duration of blower prepurge BLOW PRE...

Страница 41: ...st boiler outlet temperature Press UP DOWN for 1 sec to clear INLET HI All Records the highest boiler inlet temperature Press UP DOWN for 1 sec to clear INLET LO All Records the lowest boiler outlet t...

Страница 42: ...he outdoor temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjustable It is factory set at 70 F water temperature Boil START...

Страница 43: ...at loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the OUT DESIGN...

Страница 44: ...WIRING DIAGRAM 44...

Страница 45: ...cannot reach your gas supplier call the fire department Use only your hand to close the gas supply shut off valve outside the heater Never use tools If the knob will not turn by hand do not try to re...

Страница 46: ...d supplied on the 700A and 850A 4 Attach a 12 scale manometer to the downstream fitting on the gas manifold Measure point B in Fig 41 field supplied on the 700A and 850A 5 Attach a 12 scale manometer...

Страница 47: ...pen Look into the sight glass located at the bottom of the front panel to check igniter opera tion 3 The boiler ignites at 3000 RPM as indicated on the LCD display of the user interface 4 This boiler...

Страница 48: ...ite after pre purge time delay 8 Check to see that the high limit control is set above the design temperature requirements of the system For multiple zones Check to make sure the flow is adjusted as r...

Страница 49: ...ide front panel on boiler OPERATION Lighting Instructions 1 Before lighting make sure you have read all of the safety information in this manual 2 Set the thermostat to the lowest setting 3 Turn off a...

Страница 50: ...Item Description and Troubleshooting OUTLET SEN Check the outlet water sensor and its wiring LIMIT SEN Check the high limit sensor and its wiring INLET SEN Check the inlet sensor and its wiring GAS P...

Страница 51: ...n Lockout Fault Check the gas supply See table for more information 4 flashes N A N A 5 flashes Low Voltage Fault Check the 24 VAC input voltage The voltage must be above 18 0 VAC 6 flashes N A N A 7...

Страница 52: ...hould be no resistance Fig 43 Direct Spark Igniter Water Sensor Outdoor Sensor Water Temperature F Resistance ohms 32 32550 41 25340 50 19870 59 15700 68 12490 77 10000 86 8059 95 6535 104 5330 113 43...

Страница 53: ...ate drain is inspected and ensure that condensate is being directed to appropriate con densate management system or drain as required by local codes 3 Check that area is free from combustible materi a...

Страница 54: ...r 4 Conduct a combustion test at high and low fire Carbon dioxide should be 8 5 to 9 0 at full fire for natural gas and between 9 5 to 10 0 for propane gas Carbon monoxide should be 150 ppm 5 Check va...

Страница 55: ...fol low the precautions listed for working with ceramic fibers 4 Spray the coils with clear water making sure to con fine the spray to the area being cleaned DO NOT get the back ceramic wall of the u...

Страница 56: ...y however choose to use outside combustion air for one or more of these reasons 1 Installation is in an area containing contaminants listed below which will induce acidic condensation 2 You want to re...

Страница 57: ...l horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth and...

Страница 58: ...ntamination of combustion air or use of chemical additives to water PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned t...

Страница 59: ...____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material __________________ P...

Страница 60: ...60 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: