PRINTER SPECIFICATIONS AND REQUIREMENTS
6-2
XEROX DOCUPRINT NETWORK PRINTER SERIES INSTALLATION PLANNING GUIDE FOR MODELS 4050/4090 NPS
Outlet configurations
This section discusses specifications for the DocuPrint system
outlets and the required wall outlet configurations for the U. S. /
Canada and internationally.
Note:
All power outlets must be dedicated to this equipment. When
determining the electrical connections for your system, make sure
that:
•
Each power cord has a separate circuit
•
The printer power cord configurations match your receptacle
•
Your electrical outlets are within the required specifications.
50 Hz systems:
Ensure that power connections are per local codes/
regulations.
Printer outlet voltages—60 Hz
The following table shows the voltages for the outlets on your printing
system. All power outlets must have a dedicated circuit for each
system equipment piece.
Printer power cord configurations
The following figure shows the 60 Hz power cord configuration for 30
amp NEMA 14-30R. Voltage to ground is shown for troubleshooting
purposes.
Figure 6-1.
60 Hz power configuration
Table 6-5.
60 Hz voltage requirements at power outlet
Measurement of wiring
Nominal
Range
Line 1 to neutral
120 V
105 to 127 V
Line 2 to neutral
120 V
105 to 127 V
Neutral to ground
0 V
0 to 10 V
Line 1 to line 2
208 V
181 to 220 V
Line 1 to ground
120 V
105 to 127 V
Line 2 to ground
120V
105 to 127 V
Neutral
Line 1
Ground
Line 2
105 to 127 VAC
105 to
127 VAC
105 to 127 VAC
105 to 127 VAC
0 to 10 VAC
181 to 220 VAC
NEMA
14-30R