3
Ref: XPSU1208e / XPSU1216e
S
PECIFICATION
Input Specification
VPSU1208e
VPSU1216e
Voltage (rated)
100-240V ac 100-240V ac
Voltage (operating)
90-264V ac 90-264V ac
Frequency
50-60Hz 50-60Hz
Mains Input Fuse (Terminal)
T2.0A HRC
T3.15A HRC
Module fuse - Mains
T2.0A HRC
T2.0A HRC (x2)
Max standby Power
0.5W (no load connected)
1.0W (no load connected)
Max Mains Input Current
1.5A
3.0A
Output Specification (per power module)
Voltage
11.4 – 12.6V dc (12V dc nominal)
Note: Please factor this load ‘Voltage variance’ in when designing systems
Max load current (per module)
4A
Ripple
150 mV pk-pk max
Module Output Fuse
F4.0A
Load output Fuse
See Model Specification Table below
Overload
Electronic shutdown until overload or short circuit removed
Local Indicators
MAINS LED (Green)
Mains present
FAULT LED (Red)
Fault present: Output fuse fail
(requires load to be connected)
Fused Outputs
Model:
XPSU1208e
XPSU1216e
No. of Fused outputs:
8
16
PTC (auto resetting) Fuse Value:
[as fitted in fused output module(s)]
8 x 500mA
16 x 500mA
Mechanical
XPSU1208e
XPSU1216e
Enclosure Dimensions
h x w x d (mm) [external]
188 x 205 x 60
310 x 245 x 60
Weight
1.5Kg
2.7Kg
Environmental
Temperature
-10 to +40°C (operating) 95% RH non-condensing
-20 to +80°C (storage)