Default Settings and Ranges
975-0240-01-01
B–5
Grid Support Menu
Gen Support Menu
Item
Default
Range
Step Size
24 V
48 V
24 V
48 V
Grid Supp Volts
27.0V
54.0V
23.0–29.0V
46.0–58.0V
0.1V
Max Sell Amps
27A
0–60A
a
a.This setting is restricted to the selected AC1 breaker size.
1A
Load Shave Amps
48A
0–48A
1A
Load Shave Start
b
b.When Load Shaving is enabled, if Load Shave Start and Load Shave Stop are
set to the same time, the XW Inverter/Charger load shaves continuously.
n/a
12:00 AM–11:59 PM,
00:00–23:59
n/a
Load Shave Stop
n/a
12:00 AM–11:59 PM,
00:00–23:59
n/a
Setting
Default
Range
Step Size
GenSupp Mode
Disabled
Enabled, Disabled
n/a
GenSupp Amps
10A
4–48A
1A