Installation
22
975-0171-01-01
Connecting AC Input Wires
Figure 5 shows the wiring compartment, which contains a grounding bus (used to
wire the AC input and output gound wires) and a terminal block (used to wire the
AC input and AC output connections).
When making the AC input and AC output connections, observe the correct color
code for the appropriate AC wire, as described in Table 2 on page 11.
To make the AC input connections:
1. Locate the wiring compartment cover panel and remove the four screws.
2. Remove the cover panel from the unit to access the wiring compartment.
3. Remove one of the AC knockouts from the front or side of the unit. Do not
leave the knockout inside the wiring compartment.
4. Install a strain-relief clamp in the AC knockout.
5. Run the AC wiring through the strain-relief clamp.
6. Strip approximately 2 inches (50 mm) off the jacket from the AC cable and
separate the wires.
Figure 5
AC Wiring Compartment
CAUTION: Equipment damage
The terminal block is split into INPUT and OUTPUT sections. Damage may occur if the
unit is wired incorrectly.
Do not remove or loosen factory installed wiring.
Grounding bus
Terminal block
Содержание RS3000
Страница 1: ...RS3000 Sine Wave Inverter Charger Installation Guide RS3000 ...
Страница 2: ......
Страница 3: ...RS3000 Sine Wave Inverter Charger Installation Guide ...
Страница 8: ...iv 975 0171 01 01 ...
Страница 16: ...xii ...
Страница 48: ...Installation 32 975 0171 01 01 Figure 11 Connecting the BTS Cable to Battery Temp jack ...
Страница 55: ...Installation 975 0171 01 01 39 Figure 15 Inverter Charger Dimensions 14 2 361 ...
Страница 65: ......