Operation
Accumulated Status, Status, and Fault Registers
50
Operating Manual for RS-232 for XT/HPD Series Power Supply
Table 3.8
Accumulated Status, Status, and Fault Registers
Notes:
1.
Only CC, CV, OV, SD, ERR and FOLD can be masked or unmasked.
2.
The error (ERR) bit is reset in the accumulated status, status, and serial poll registers with an
error query (ERR?).
3.
The accumulated status register is cleared with an accumulated status query (ASTS?).
4.
A fault is cleared with a fault query (FAULT?).
Condition
Mnemonic Bit Position Bit Weight
Constant voltage operation
CV
0
1
Constant current operation
CC
1
2
Not used
–
2
4
Overvoltage protection tripped
OV
3
8
Not used
–
4
16
Supply external shutdown active (J7-1)
SD
5
32
Foldback mode operation
FOLD
6
64
Remote programming error
ERR
7
128
Power ON (accumulated status, status
registers only)
PON
8
256
Remote mode (accumulated status, status
registers only)
REM
9
512