SECTION 3
INSTALLATION AND INITIAL TURN-ON
PV-225208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.
DOCUMENT: 151811
3-2
All wiring methods shall be in accordance with the National Electrical Code ANSI/
NFPA 70. All power conductors interfacing to the PV-225208 should be sized in
accordance with the National Electric Code ANSI/NFPA 70 and local codes. Large
gauge wire must have a minimum bend radius dependent upon the wire gauge (refer
to the National Electric Code, Article 373-6B). Take care to keep the wire bundles
away from any sharp edges which may damage wire insulation over time. Xantrex
Technology recommends using 250 MCM, 105 degrees C, minimum, copper wire
for all connections to the PV-225208.
CAUTION
INSTALLATION INSTRUCTIONS
Ventilation Considerations
Maintain a minimum of 12” clearance in back , front and both sides of the PV-225208 for proper cooling fan
operation.
Installation
1. Move the PV-225208 into place. Lift the PV-225208 from beneath the lower enclosure with a forklift as
shown in
Figure 3-1
. (See following page.)
2. Anchor the lower enclosure feet to the floor with a 1/2” anchor bolts.
3. Install all conduits needed for cable entry in the shaded areas of both AC and DC interface enclo-
sures as shown in
Figure 3-2
. (See following page).
Termination
Wire Range AWG
Compression Lug (AC)
Up to 4 600MCM-#2
Conductors Per Phase
Compression Lug (DC+ and
DC-)
Up to 8 600MCM-#2
Conductors for each (+) and
(-)
Terminal Block (DC Neutral)
Up to 2 350MCM-#6
Conductors
The following table shows acceptable wire gauges to be connected to the PV-225208 AC and DC inputs.
Wire Gauge Table