Specifications
A–6
975-0334-01-01
GT3.3
Input
Output
GT3.3N-NA-240/208 UL-05
GT3.3-NA-240/208 UL-05 GT3.3-NA-240/208-POS UL-05
Model number
864-1006
864-1004
864-1005
Input voltage, Maximum
Power Point range
Certified operating range:
200–400 Vdc. (Unit is operable
as high as 550 Vdc.)
Certified operating range: 195–550 Vdc.
(Unit is operable as low as 193 Vdc.)
Absolute maximum array
open circuit voltage
600 Vdc
Maximum input current
17.5 Adc (240 V),
16.5 Adc (208 V)
18 Adc (240 V), 17 Adc (208 V)
Maximum array short circuit
current
24 Adc
Reverse polarity protection
Short circuit diode
Ground fault protection
GF detection, I
DIF
> 1 A
Nominal output voltage
240 V
208 V
Maximum output power
3300 W
3100 W
Operating range, utility voltage (phase to phase)*
*
Factory settings can be adjusted with the approval of the utility. This unit is provided with adjustable
trip limits and may be aggregated above 30 kW on a single Point of Common Coupling. See “Ad-
justable Voltage, Frequency and Reconnection Settings” on page A–10.
212–263 Vac
184–228 Vac
Operating range, utility voltage (phase to neutral)
*
106.1–131.5 Vac
Nominal output frequency
60 Hz
Operating range, utility frequency*
59.3–60.5 Hz
Startup current
0 Aac
Maximum continuous output current
13.8 A
14.9 A
Maximum output fault current
20 A
Maximum output overcurrent protection
20 A RMS
Maximum utility backfeed current
0 A
Total Harmonic Distortion
<5%
Power factor
>0.99% (at rated power), >0.95% (full power range)
Utility monitoring— islanding protection
Vac, fac as per UL 1741 (2005)
Output characteristics
Current source
Output current waveform
Sine wave