Operating During Transition Between Grid Mode and Battery Mode
70
Freedom XC 2000 (230VAC) Owner's Guide
Overload Conditions
There are two kinds of overload conditions – an overload warning
and an overload shutdown.
Overload
Warning
When the Freedom XC’s AC load is approximately 100 W
below the overload shutdown limit of rated watts, the
audible alarm beeps once and the LCD screen shows a
warning code
E06
.
Overload
Shutdown
When the Freedom XC’s AC load increases to near
~2100 W, the audible alarm beeps every 5 s for 1 min
and the LCD screen shows a error code
E03
. The Status
LED turns solid RED.
High Surge Loads
Some induction motors used in freezers, pumps, and other motor-
operated equipment require high surge currents to start. The
Freedom XC may not be able to start some of these motors even
though their rated steady state current draw is within the
inverter/charger’s limits. The unit will shut down and indicate an
overload shutdown.
Over-temperature Conditions
During inverter operation, when the Freedom XC’s internal
temperature starts to approach its preset shutdown limit, the
display will show error code
E07
. If the over-temperature condition
persists, the display will show error code
E04
. The Status LED
turns solid RED and the inverter/charger will shut down to prevent
damage to the inverter/charger and protect the battery from being
over-discharged.
Содержание Freedom XC 2000
Страница 1: ...Freedom XC 2000 230VAC Inverter Charger Owner s Guide Freedom XC 2000 230VAC 817 2080 12...
Страница 20: ...This page is intentionally left blank 2...
Страница 28: ...This page is intentionally left blank 2...
Страница 32: ...This page is intentionally left blank 2...
Страница 98: ...This page is intentionally left blank 2...
Страница 103: ...This page is intentionally left blank 2...