Basic Installation Procedures
975-0767-01-01
49
7. Unpack the customer-supplied GFCI receptacle and lay out
the GFCI unit and the two mounting screws. See
Fault Circuit Interrupters (GFCIs) on page 33
for information
on compatibility.
8. Prepare the following:
l
1 × 5" (127mm) black AC wire (for Line connection)
l
2 × 5" (127mm) white AC wire (for Neutral connection)
l
2 × 5" (127mm) green AC wire (for Ground connection)
l
3 × spade ferrules
l
3 × straight ferrules
l
3 × twist-on wire connector (marrettes)
9. Using the labeled diagram in
, strip,
terminate the wires with straight or spade ferrules, and
connect the wires to the correct terminals.
10. Replace the wiring compartment cover (using a #2 Phillips
torque screwdriver - see WARNING), if you are finished with
connecting all the AC wires in the unit.
WARNING
ELECTRICAL SHOCK HAZARD
Use a torque screwdriver to tighten the captive nut panel screw to
5 in-lb (0.56 N-m) torque of force to ensure a proper ground
connection and a required tool access to the wiring compartment.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
11. End of
GFCI with AC Output Wiring Connections
.
Figure 13 Parts inside the AC compartment
4a
4b
1a
1b
5
6
8
9 10 11
12
L G
AC OUT
N
N G
AC IN
L
7
13
14
14a
14b
14c
3a
3b
3c
3d
2c
2b
2a
2d
1
5" (127mm) black stranded wire.
1a
(stripped) and
1b
(straight ferrule)
2
5" (127mm) green stranded wire.
2a
(spade ferrule) and
2b
(stripped)
5" (127mm) green stranded wire.
2c
(stripped) and
2d
(straight ferrule)
3
5" (127mm) white stranded wire.
3a
(spade ferrule) and
3b
(stripped)
5" (127mm) white stranded wire.
3c
(stripped) and
3d
(straight ferrule)
4
15 A supplementary protector with two wires
4a
(bottom, spade ferrule) and
4b
(top, stripped)
5
GFCI's
LOAD
terminals (top and bottom). The two terminals may or may not be covered by a
yellow tape.
c
DO NOT REMOVE THE TAPE
.
6
GFCI's
LINE
for Neutral. Silver terminal (bottom)
7
GFCI's
LINE
for Live. Brass terminal (top)
8
GFCI's Ground terminal (green)
9
Inverter AC OUT - (
L
)ine terminal
10
Inverter AC OUT - (
G
)round terminal
11
Inverter AC OUT - (
N
)eutral terminal
12
GFCI's mounting screws. Use the two outer holes.
13
Twist-on wire connectors
14
3-wire AC cable, stripped