Freedom SW 230V Installation Guide
Installing the Inverter/Charger
Connecting AC Input Wires
Figure 6 shows the wiring compartment, which contains a
grounding bus (used to wire the AC input and output ground
wires) and a terminal block (used to wire the AC input and
AC output connections).
When making the AC input and AC output connections,
observe the correct color code for the appropriate AC wire, as
described in Table 1 on page 13.
To make the AC input connections:
1. Locate the wiring compartment cover panel and remove
the four screws.
2. Remove the cover panel from the unit to access the wiring
compartment.
3. Remove one of the AC knockouts from the front or side
of the unit. Do not leave the knockout inside the wiring
compartment.
4. Install a strain-relief clamp in the AC knockout.
5. Run the AC wiring through the strain-relief clamp.
Figure 6
AC Wiring Compartment
NCORRECT BATTERY
P
OLA
R
ITY
W
ILL
CA
U
SE
DA
M
A
GE
T
O
WIRING BOX COVER MUST BE IN PLACE DURING
OPERATION TO REDUCE RISK OF INJURY TO PERSONS.
30A
CHARGER
A
C
INPUT
30A
INVER
T
ER
A
C
INPUT
AC
IN
AC
OUT
AC GROUNDS
(BEHIND COVER)
To ground bus
EQUIPMENT DAMAGE
The terminal block is split into INPUT and OUTPUT sections. Damage may
occur if the unit is wired incorrectly.
Do not remove or loosen factory installed wiring.
Failure to follow these instructions can damage the unit and/or damage
other equipment.
FSW 230V Installation Guide.book Page 26 Tuesday, August 7, 2018 9:18 AM