![Xantrex Freedom SW 2000 Скачать руководство пользователя страница 20](http://html2.mh-extra.com/html/xantrex/freedom-sw-2000/freedom-sw-2000_installation-manual_3153294020.webp)
6
Freedom SW 2000 Installation Guide
Planning the Installation
Figure 3
Wiring and Breakers Blo
c
k Diagram
IMPORTANT: Read Owner’s and Installation Guides
prior to installation.
Always refer to local and national
electrical codes for proper wire and
breaker sizes prior to installation.
FSW 2000
Inverter/Charger
120 V AC OUT
120 V AC IN
12 volt
Battery (Bank)
4/0 AWG
250 A fuse**
8 AWG Chassis GND
10 AWG
10 AWG*
HOT = BLACK
NEUTRAL = WHITE
GND = GREEN/Bare
HOT BUS
HOT BUS
TO AC APPLIANCE
LOADS
INVERTER AC SUB PANEL (TYPICAL)
MAIN ELECTRICAL PANEL
FROM SHORE OR
GENERATOR POWER
OPTIONAL
GFCI duplex receptacle
15 A output limit
HARDWIRE CONNECTIONS
20 A MAX in inverter
30 A MAX In pass-through
** Class T or equivalent
Neutral
GND
15 A
20 A
Neutral
GND
30 A
MAIN
For wire and breaker size information:
1.See “AC Input Protection” on page 7.
2.See “AC Output Protection” on page 8.
3.See “GFCI Requirements” on page 8.
4.See “AC Wiring” on page 9.
5.See “DC Cabling” on page 11.
6.See “DC Grounding” on page 11.
1
2
3
4
4
5
6