Operating During Transition Between Grid Mode and Battery Mode
975-0821-01-01
69
Operating
Condition
Battery
Voltage
Comment
Low
Voltage
Shutdown
< LBCO
The buzzer sounds a single 1 s
low battery alarm beep and the
LCD screen shows error code
E01
. After LBCO Shutdown
delay timer runs out, the unit
shuts down inverter output. The
buzzer stops beeping and the
LCD screen shows error code
E01
.
Instant Low
Voltage
Shutdown
< 9.0 V
After 2 s below the limit, the unit
shuts down inverter output
completely. LCD screen turns
off completely.
Operating
Condition
Battery
Voltage
Comment
High
Voltage
Shutdown
17.0 V
The display shows error code
E02
alternating with the battery
voltage. The red status LED
turns on.
NOTE:
Although the Freedom
XC incorporates over-voltage
protection, it can still be
damaged if input voltage
exceeds 18.0 V