Freedom SW 230V Installation Guide
Stacking Features
(e.g., 2100 watts on Freedom SW 3524-230), the Slave unit
will assist the Master and the two will share the load equally.
Should the load on the Master drop below 20% of rated load
(700 watts for Freedom SW 3524-230), the Slave unit
disengages and returns to a waiting state.
Search mode disabled
The Slave unit operates
continuously along with the Master unit and shares the load.
Wiring Schematic
NOTE
: Please refer to the Stacking Configuration sheet that
shows the wiring schematic employed between two Freedom
SW 230V inverter/chargers that are stacked in parallel.
IMPORTANT
: Follow the same guidelines in “Installing the
Inverter/Charger” on page 18 when choosing cables and/or
wires for AC and DC connections.
FIRE, ELECTRICAL SHOCK, AND ENERGY HAZARDS
Make sure all wiring being used to make stacking configurations between
inverter/chargers is disconnected (physically or by opening the breaker)
from all electrical sources before handling. All wiring must be done in
accordance with local and national electrical wiring codes.
Failure to follow these instructions will result in death or serious injury.