40
5.2.2 LED display table
Remark
<80%
>80%
100%
x
Operating status prior to starting the charging cycle
Charging characteristic 12 V
(P0) set
x
5sec.flashing(1x/sec.)
Charging characteristic 24 V
(P1) set
x
x
5sec.flashing(1x/sec.)
Battery voltage > 2.4V/Z
flashing
red
charging is started
automatically if the value falls
below the limit
Battery missing or polarity
reversed <0.25 V/cell
red
Permanently lit
Operating status during the charging cycle
Deep discharge start
Flashing
Battery voltage
>0.25 V/cell
<1.9 V/cell
Main charge
x
Recharging
x
Charging end current
(2.4 V/cell) reached
End or charge/charge retention
x
Pause
x
x
Alternatingflashing
Operating status in the event of an error
Temperature error
x
red
Control error
x
red
Timeout
x
red
Also shutdown by current
consumption test or deep
discharge start
6 Maintenance
6.1 Maintenance plan
Interval
Maintenance activity
By who?
before each
commissioning
Visually inspect the device and its peripherals for possible damage
and contamination. Clean if necessary.
Operator
Checkconnectionsforsecurefit
Checkpersonalprotectiveequipmentforfunctionalityandreplace
if necessary.
Check the operating environment for compliance with the
operating conditions.