GTW-LAN
Product information
Functional earth connection
Note!
We expressly point out that the functional earth connection must be connected with the
accompanying cable and the earth terminal. The earth terminal must be placed on the
top-hat rail. Earthing is required to ensure trouble-free function.
Technical data
Supply voltage
230 V~, +10%/-15%, approx. 6VA
Inputs
1 x 230V~, day/night signal (light contact)
1 x 230V~, service operation
Output relay, central alarm
2 x relays, changeover contact, 230V~, 4(2)A
Communication
3-wire CAN bus interface with integrated supply voltage,
electrically isolated (RJ45 socket or terminals 1-5)
Service connection socket
CAN bus interface; 3.5mm jack socket
Network interface
Ethernet connection (10Mbit/s, RJ45 socket)
Housing
Plastic
Dimensions
(WxHxD) 160 x 90 x 58mm, DIN 43880
Mounting
Mounting rail DIN EN 50022 35x15
Ambient temperature
Operation: 0...+50°C, storage: -25...+70°C
Weight
Approx. 600g
CE conformity
EC conformity according to
-2004/108/EC (EMC Directive)
-2006/95/EC (Low Voltage Directive)
RoHS
Valid from
Version 1.0
Note!
This document will automatically become invalid when superseded by a new technical
description.
Page 4 of 4
Subject to technical changes
GTW-LAN_PI_2015-02_EN