DIN-XP
Input module
with 16 operation or fault inputs
Page 4 of 4
Subject to technical changes
DIN-XP_V2.7.0_PI_2019-04_EN
Place the device with the upper guide edge on
the top-hat rail.
Then press the device gently downward until it
engages with the fastening safety catch on the
top-hat rail.
For wiring of the data lines, we recommend the use of standard telephone lines 2x2x0.8ø. up to
lengths of 100m. The shielding must be grounded in the control cabinet. For cable lengths from 100m
to 400m, shielded lines with braided sheathing should be used.
We recommend the use of shielded cables for sensor extension.
Cable length
Cross section
Up to 100m
0.75mm²
Up to 400m
1.5mm²
Technical data
Power supply
230V~, +10% / -15%, approx. 4VA
Digital inputs
16 x for 230V~ (common neutral conductor)
Output relay
2 x changeover contacts, 230V~, 4(2)A
Central unit
Single-chip microcomputer, data memory
Monitoring system
Self-monitoring of data memory and microcomputer
Communication
3-wire CAN bus interface with integrated power supply,
galvanically isolated, service socket
Gateway types
The device is supported by the gateways:
Multigate, from V1.0
CMD300, from V1.0
GTW-LAN 2.1
Global fault evaluation is supported by the gateways:
Multigate, from V2.4
CMD300, from V1.0
GTW-LAN 2.1
Dimensions
(WxHxD) 106 x 90 x 58mm (DIN 43880)
Fastening
Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature
Operation: 0...+55°C, storage: -25...+70°C
Weight
About 450g
CE conformity
−
2014/30/EU (EMC Directive)
−
2014/35/EU (Low Voltage Directive)
EAC conformity
−
TR CU 004/2011
−
TR CU 020/2011
RoHS II
Valid from
Version 2.7.0