background image

DIN-XP 

 

Input module 
with 16 operation or fault inputs 

 

Page 4 of 4 

Subject to technical changes 

DIN-XP_V2.7.0_PI_2019-04_EN 

 

 
Place the device with the upper guide edge on 
the top-hat rail. 
Then press the device gently downward until it 
engages with the fastening safety catch on the 
top-hat rail. 

 
For wiring of the data lines, we  recommend the use of standard telephone lines 2x2x0.8ø. up to 
lengths of 100m. The shielding must be grounded in the control cabinet. For cable lengths from 100m 
to 400m, shielded lines with braided sheathing should be used. 

We recommend the use of shielded cables for sensor extension. 
 

Cable length 

Cross section 

Up to 100m 

0.75mm² 

Up to 400m 

1.5mm² 

 
 

Technical data 

 

Power supply 

230V~, +10% / -15%, approx. 4VA 

Digital inputs 

16 x for 230V~ (common neutral conductor) 

Output relay 

2 x changeover contacts, 230V~, 4(2)A 

Central unit 

Single-chip microcomputer, data memory 

Monitoring system 

Self-monitoring of data memory and microcomputer 

Communication 

3-wire CAN bus interface with integrated power supply, 
galvanically isolated, service socket 

Gateway types 

The device is supported by the gateways: 
Multigate, from V1.0 
CMD300, from V1.0 
GTW-LAN 2.1 
Global fault evaluation is supported by the gateways: 
Multigate, from V2.4 
CMD300, from V1.0 
GTW-LAN 2.1 

Dimensions 

(WxHxD) 106 x 90 x 58mm (DIN 43880) 

Fastening 

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715) 

Ambient temperature 

Operation: 0...+55°C, storage:  -25...+70°C 

Weight 

About 450g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive) 

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 2.7.0 

 