WURM DCC-BL Скачать руководство пользователя страница 4

Compound and condenser controller with operating modes for compressors with FC

4

 DCC-BL_V1.1.0_PI_2019-04_EN

Subject to technical modifications

DCC-BL

1.5 

Installing the device

This device is designed for top-hat rail installation. The housing has standard dimensions according
to DIN 43880 and is also suitable for operation in fuse boxes and distribution cabinets. 
The devices can be positioned immediately adjacent to one another without gaps.

WARNING

DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!

Switch  off  the  power  to  the  entire  plant  before  installing.  Otherwise,  mains  voltage  and/or
external voltage may still be present, even if the control voltage is switched off. Always remove
both power plugs (L and N).

The entire plant must be free of voltage.

1.

(A) 

Place the device with the leading edge at an acute angle to the top-hat rail.

2.

(B)

 Push the device downwards onto the top-hat rail.

The device snaps into place with the fastening safety catch 

(a)

 on the top-hat rail.

You can now connect the device.

Fig. 3: Top-hat rail installation

1.6 

Technical data

Power supply

230V~, +10% / -15%, max. 9VA

Display

1 x display with text display

2 x green LEDs, C-BUS data traffic (CAN Tx, CAN Rx)

Communication

3-wire CAN bus interface with integrated power supply, 

galvanically isolated, separate service socket

Communication

Expansion module

Interface for connecting X-tra module

Pressure sensors

For p

and p

C

 (corresponds to 4...20mA):

DAR7(-0.5...7bar)

DAR25 (0...25bar)

DAR40 (0...40bar)

DAR60 (0...60bar)

DAR120 (0...120bar)

Temperature sensor

TRK277, DGF, T2015, T3000, TF201/231, K243

Control input

0...10V= (for output control in voltage control operating mode) 

or alternatively temperature sensor TRK277

Digital inputs

4 x potential-free

Output relay

4 x normally open contacts, 230V~, 4(2)A,

Rated voltage 230V~

Analogue outputs

2 x 0...10V=, non-floating, max. load 10mA

Real-time clock

Power reserve

Monitoring system

Monitoring of data memory and connected sensors

Dimensions

(W x H x D) 106mm x 90mm x 58mm (DIN 43880)

Fastening

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)

Ambient temperature

Operation: 0...+55°C, storage: -25...+70°C

Weight

About 320g

CE conformity

-

2014/30/EU (EMC Directive)

-

2014/35/EU (Low Voltage Directive)

RoHS II

Valid from

Version 1.1.0

A

B

Отзывы: