CRD-XP installation 

The CRD-XP controller is 

installed

 in the refrigerat

ion unit

 or control cabinet door. 

1. Attach the frame clips on the left and right of the installation

frame wall.

2. Connect the controller wires.

3. Place the controller on the guide rails of the frame clips and

push it into the installation frame.

4. Align the sealing frame in the back of the front panel and

press in firmly.

5. Place the front panel with sealing frame on the controller.

6. Press the front panel in until it is heard to engage.

Technical data 

Power supply 

Through transformer TR9-9-4 

Digital inputs 

2 x floating (multifunction inputs) 

Temperature sensor 

3 x TRK277/7 PLUS, DGF, T20015, K243 

Output relay 

1 x fan, normally open contact, 230V~, 3(2)A 
1 x cooling, normally open contact, 230V~, 3(2)A 
1 x defrost, normally open contact, 230V~, 3(2)A 

The total current of these output relays must not exceed 12A. 

Communication 

3-wire CAN bus interface with integrated power supply, galvanically
isolated, service socket

Communication EEV data 

4-wire RS485 interface with power supply, galvanically isolated

Analogue output 

Min. load resistance 

Accuracy 

1 x 0…10V=, non-floating, short-circuit proof 

2.5kΩ / 10kΩ

 

<3% / <1% 

Connections 

Spring-loaded terminals 

Housing 

Plastic 

Dimensions 

(W x H x D) 158 x 32 x 75mm 

Fastening 

In the installation cut-out with holding clips and sealing frame 
(120 x 28mm) 

Ambient temperature 

Operation: 0...+55°C, storage: -25…+70°C 

Weight 

About 150g 

CE conformity 

2014/30/EU (EMC Directive)

2014/35/EU (Low Voltage Directive)

EAC conformity 

TR CU 004/2011

TR CU 020/2011

RoHS II 

Valid from 

Version 3.9.8 