Interface for the Modbus RTU
MIQ/2-MOD
24
ba75973e01
07/2012
8
00h
Contents of register 11 (HI)
= status info
0000h (Int 16)
--> no errors
9
00h
Contents of register 11 (LO)
= status info
10
00h
Contents of register 12 (HI)
= measuring mode
00h (Int 8) --> FNU
Trüb
11
14h
Contents of register 12 (LO)
= measured value status
14h (Int 8)
Main measured value
(bits 7-4):
1h --> VALID
Secondary measured
value (bits 3-0):
4h --> MISSING
12
42h
Contents of register 13 (HI)
= main measured value
429E46C2h (Float 32)
--> 79,1382
Measured parameter
and unit, see byte 10
(measuring mode)
13
9Eh
Contents of register 13 (LO)
= main measured value
14
46h
Contents of register 14 (HI)
= main measured value
15
C2h
Contents of register 14 (LO)
= main measured value
16
00h
Contents of register 15 (HI)
= secondary measured
value
00000000h (Float 32)
--> 0
but measured value
invalid (MISSING),
see Byte 11 (mea
-
sured value status)
17
00h
Contents of register 15 (LO)
= secondary measured
value
18
00h
Contents of register 16 (HI)
= secondary measured
value
19
00h
Contents of register 16 (LO)
= secondary measured
value
20
23h
CRC (HI)
Checksum (CRC)
21
5Eh
CRC (LO)
Modbus response
Byte
Value Information
Meaning of the value
Содержание MIQ/2-MOD