Commissioning
IFL 70x IQ
3 - 12
ba75990e01
10/2012
Establishing time
0 ...
120
... 600 sec
Filter that ignores (interfering) echoes
whose residence time within the ultra-
sonic cone is shorter than the time defined
here.
Example: To ignore a scraper, the maxi-
mum duration of its visibility in the ultra-
sonic cone has to be entered.
Temperature
0.0 ...
15.0
... 50.0
The temperature affects the speed of
sound in the measuring medium. This
effect can be taken into account by enter-
ing the temperature value.
Enter the average water temperature at
the average water depth of the basin.
If there are seasonal fluctuations of the
average water temperature we recom-
mend to set a different average tempera-
ture for summer and winter.
Save and quit
The sensor stores all changed settings
and the display switches to the next
higher level.
Quit
The display switches to the next higher
level without saving the new settings.
Setting
Selection/values
Explanation
Содержание IFL 700 IQ
Страница 1: ...ba75990e01 10 2012 IFL 700 IQ IFL 701 IQ Operating manual IQ SENSOR NET Sludge level sensor IFL 700 IQ...
Страница 8: ...Overview IFL 70x IQ 1 4 ba75990e01 10 2012...
Страница 24: ...Commissioning IFL 70x IQ 3 14 ba75990e01 10 2012...
Страница 26: ...Measuring IFL 70x IQ 4 2 ba75990e01 10 2012...
Страница 30: ...Maintenance cleaning accessories IFL 70x IQ 5 4 ba75990e01 10 2012...
Страница 34: ...What to do if IFL 70x IQ 6 4 ba75990e01 10 2012...
Страница 38: ...Technical data IFL 70x IQ 7 4 ba75990e01 10 2012...
Страница 40: ...Indexes IFL 70x IQ 8 2 ba75990e01 10 2012 8 1 2 Info messages The sensor does not generate any info messages...
Страница 42: ...Indexes IFL 70x IQ 8 4 ba75990e01 10 2012...
Страница 43: ......