Original Operating Instructions
BATD0100-ES-1-480-1 (Outdoor)
Installation
O_BATD0100-ES-1-480-1_(Outdoor)_V2.2_US
Page
69
of
110
5.5.1.3 DC Connection
Prerequisites:
If the battery has no circuit breaker or fuse, a circuit breaker or fuse shall
be installed between the battery and inverter which is able to securely
switch off the short-circuit current of the battery under fault conditions.
Required material:
•
2 x M10x35 millimeter hexagon screw
•
2 x
10.2 millimeter conical spring washer
Figure 23: DC connection
Pos.
Description
1
DC circuit breaker
2
DC (+)
3
DC (-)
5
Cable clamps
6
Cable entry grommets
Procedure:
1.
Check
correct polarity (Figure 23).
2.
Route
cables through the cable entry grommets.
3.
Connect
the DC (+) and DC (-) cables to the corresponding terminals.
4.
Tighten
the screws with a torque of
44 Nm
(390 lb-in). The compression
cable lug must be suitable for a M10 screw.
5.
Fix
the cables with cable clamps.
Содержание BATD0100-ES-1-480-1