Troubleshooting
O_BATD0050-ES-1-400-1_V2.6_GB
Page
57
of
72
Table 5: Extract of BAT Error Codes (continued)
Code Error Description
Corrective Action
157
OV-Protection_/_Filter_Fuses
Check OV-Protection
158
Insulation Error
Check Insulation
159
Voltage_Measurement_Failed
Check voltage measurement
161
Inverter_HW_Error_L1
Check Powerstack
162
Inverter_HW_Error_L2
Check Powerstack
163
Inverter_HW_Error_L3
Check Powerstack
164
Port_Idc_error
Check Idc-Sensor connection
169
Precharge_DC-Link
Check Precharge circuit
Check DC-Source
171
Grid_rotation
Check gird rotation
172
Switch_on_condition failed
Check Grid voltage / frequency
174
Frequency_error
Check frequency
175
Island_Grid_detected
Check Grid voltage
6.1.1 BAT Error Codes 11-21
Corrective action:
1.
Clean
the cooling air inlet and outlet (Figure 9
6.1.2 BAT Error Codes 22-29
Corrective action:
1.
Check
if the ambient temperature is within the specified limits (Table 11).
6.1.3 BAT Error Codes 66-68, 71-73, 76-78, 116-118, 121-123, 126-128, 175
Corrective action:
1.
Ensure
that the motor protecting switch (-F31) is in position
I
.
2.
Measure
the AC voltage.
3.
Check
if the values are within the specified limits.
The values can be seen in the Interface Description
.
6.1.4 BAT Error Codes 81, 82, 131, 132
Corrective action:
1.
Measure
the DC voltage (Section 4.2).
2.
Check
if the values are within the specified limits.
The values can be seen in the
Interface Description
.
6.1.5 BAT Error Codes 151, 155
Corrective action:
1.
Check
if the AC circuit breaker is in position
TRIPPED
.
If the AC circuit breaker is in position
TRIPPED
, then
switch
the
AC circuit breaker in position
OFF
.
Afterwards
switch
the AC circuit breaker in position
ON
.