7.1.1.4 Torque Check of Electrical Connections
Maintenance tasks:
a.
Open
doors.
b. Check connections and connectors of all parts for tightness.
If connections are loose, please
contact
customer service (Section 10).
Tighten
with specific torque
.
c.
Check
grounding connection, AC connection and DC connection for tightness.
If connections are loose,
tighten
with shown torque (Table 6).
d.
Check
insulation and electrical connection for discolouration or corrosion.
In case of discolouration or corrosion,
renew
the connection.
e.
Close
doors.
Table 6: Torque of electrical components
Connection
Torque
Grounding
44 Nm
AC connection
75 Nm
DC connection
75 Nm
7.1.1.5 Check of Cable and Line Condition
Maintenance tasks:
a.
Open
doors.
b.
Check
all cables and lines for damages.
In case of damage,
renew
cables and lines.
c.
Close
doors.
7.1.1.6 Check of Fuse Condition
Maintenance tasks:
a.
Open
doors.
b.
Check
if fuses are triggered.
If fuses are triggered,
renew
the fuses. (Section 11.1).
c.
Close
doors.
7.1.1.7 Functional Test of DC Switch Disconnector
Maintenance tasks:
a.
Open
doors.
b.
Check
the continuity of the DC switch disconnector (-Q1) when it is
switched on.
If the DC switch disconnector has no continuity,
replace
it.
c.
Check
the continuity of the DC switch disconnector (-Q1) when it is
switched off.
If the DC switch disconnector has continuity,
replace
it.
d.
Close
doors.