Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Installation
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
37
of
69
3.5.1.6 Option Island Grid Function
If the product has the island grid function, an external voltage (+24 V
DC
) must be
applied on the terminals (-X17.1-2) so that the product can also operate parallel to the
grid. By disconnecting the external voltage via an external disconnecting device, the
product can establish an island grid.
The terminals (-X17.1-2) are implemented as a potential-free feedback contact. A
signal on this feedback contacts manages the switching in and out of the island grid
mode.
Figure 16: Cable routing terminal strip (-X17)
Figure 17: Wiring diagram extract
terminal strip (-X17)
Procedure:
1.
Locate
terminal strip (-X17) (Figure 16).
2.
Open
the corresponding cable ducts.
3.
Route
the cable through the cable entry grommet.
4.
Connect
power supply (+24 V
DC
) (Figure 17):
o
DC (+) to terminal (-X17.1)
o
DC (-) to terminal (-X17.2)
5.
Close
the cable ducts.
6.
Fix
the cable with a cable clamp.