Burner Control CBR
Profibus DP with CBR
Please follow all applicable safety regulations. Depicted configurations may differ from the actual scope of delivery, procedures however,
remain principally the same.
Burner control CBR with Profibus (functional schematic)
SPS,PLC,CPE
L1,N,PE
BUS
(FLOX GWS)
CBR
BUS
X2:
X2:
BUS
X2:
BUS
Power supply, Safety chain, (FLOX/Flame)
Bus wire
1
2
3
CBR
CBR
A maximum of 126 devices my be connected to a Profibus DP system (master and slaves). Each device receives an
individually defined address. The address can be entered into the CBR via the push buttons on the front panel.
The address range is from 0 to 126 (CBR delivered with invalid address 127!). All devices are connected in a bus
fashion (in line). Each individual line segment can have as many as 32 participants (masters and slaves). A bus
terminator must be placed at the beginning and end of each segment. Termination can be achieved via the switch
within each Profibus connector. To maintain fault free bus operation, each terminated device must have power
connected.
Repeaters (boosters) must be used for more than 32 devices or to extend the range of the bus network.
It is recommended to utilize shielded 2 wire cable (for example Lapp Unitronic –Best.-Nr. 2170-220T or Siemens –
Best.-Nr.6XV1830-OEH10) to protect the network against electromagnetic interference. The shield must be
connected on both ends, good conductivity of the shield is paramount. Do not switch the data lines A and B.
Furthermore, keep Profibus cables as far away from other highly radiating cables (for example, high voltage cables,
frequency converters, VFD, etc.)
Ascertain that the power potential level is compensated between various masters and slaves (uniform potential)
(Refer to Aufbaurichtlinien/ EMV-Maßnahmen im Fachbuch: “Profibus-DP/DPV1“ – Hüthig-Verlag – ISBN 3-
7785-2781-9).