Rectifying faults
E 9
and
flashing.
Safety temperature limiter has tripped.
Check
Action
1.
Is the heating pressure between 1
and 2 bar?
yes:
B
Top up system.
B
Vent appliance.
B
Press
, does appliance restart???
E9?
↓
2.
no:
↓
2.
2.
Is the pump blocked?
yes:
B
Unblock the pump.
If pump won’t start:
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change the pump.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.
B
Press
, does appliance restart???
E9?
↓
3.
no:
↓
3.
3.
Is lead disconnected from one/both
safety temperature limiters?
yes:
B
Power OFF the appliance.
B
Connect lead.
B
Turn ON the appliance.
B
Press
, does appliance restart???
E9?
↓
4.
no:
↓
4.
4.
B
Power OFF the appliance.
B
Unplug the connector from the
cut-off device.
B
Measure the NTC electrical resist-
ance.
R =
∞
?
yes:
B
Change the over heating cut-off device.
B
Connect flue gas safety temperature limiter lead.
B
Turn ON the appliance.
B
Press
, does appliance restart???
E9?
↓
5.
no:
B
Connect flue gas safety temperature limiter lead.
B
Turn ON the appliance.
E9?
↓
5.