Controls
Greenstar Ri
ErP
- 6 720 813 340 (2014/09)
3.1.3 Turning the central heating off during the summer
▶ To turn your central heating off during warm periods:
▶ Set the programmer to OFF
– Please refer to the programmer manufacturer's instructions.
-or-
▶ Turn the room thermostat temperature down to minimum.
3.1.4 Boiler frost protection
If you are leaving your property unoccupied during cold weather, please leave your programmer on constant and your room
thermostat set to 15°C.
▶ If the temperature within the boiler falls below 8°C the pump will run to circulate water and prevent the system freezing.
– If the temperature does not rise to 9°C within 30 minutes of the pump operating, the boiler will fire up to provide heat to
bring the temperature up.
▶ If the temperature within the boiler falls below 5°C the boiler will fire, bringing the boiler temperature up to 12°C to avoid the
possibility of the system freezing.
▶ This process will be repeated until such time that the boiler temperature does not drop below 5°C.
Do not switch the boiler off at the mains power switch or mains fused spur.