FAULT FINDING AND DIAGRAMS
Greenstar Highflow CDi
ErP
- 6720818077 (2016/04)
48
7.6
Condensate pump Indicator lights
The condensate pump has indicator lights [1] which show operation
status or a fault condition.
Fig. 69 Condensate pump indicator lights
6720818077-27.1W
o
CONDENSATE PUMP - OPERATING LIGHTS AND FAULT CONDITIONS:
Ready for operation = Steady green light
Fault = Red light
Pump running = Flashing green light
Operating lamps
Cause
Solution
Green
Red
Off
Off
Mains supply not connected
Power failure
Connect mains supply
Check mains and fuse/circuit breaker
Flashing
Flashing
Dry-run
(possible air in pump)
Pump restarts automatically after one minute
On
Flashing
Pump blocked
Visually inspect the pump inlet and tank.
Remove or rinse out any dirt or foreign bodies
On
On
Level exceeds alarm level
Discharge hose or non-return valve blocked
Possible kink in discharge hose
(clean or remove kink if applicable)
Off
Flashing
Pump blocked and
alarm level exceeded
Visually inspect the pump inlet and tank.
Remove or rinse out any dirt or foreign bodies