![Worcester Greenstar 8000 Style GR8700iW 30 C Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/worcester/greenstar-8000-style-gr8700iw-30-c/greenstar-8000-style-gr8700iw-30-c_installation-and-maintenance-instructions-manual_996484045.webp)
Commissioning
45
Greenstar 8000 Style – 6720883864 (2019/02)
6.11
Flue gas analysis
NOTICE:
Combustion testing
▶ Combustion testing must be carried out by a competent qualified
person. Testing must not be attempted unless the person carrying
out the combustion check is equipped with a calibrated Flue Gas
Analyser conforming to BS 7967 and is competent in its use.
Flue gas analysis
▶ Ensure that the gas inlet pressure has been checked and is
satisfactory.
▶ Refit the test point plugs after the test has been completed.
The flue gas analysis performance of the appliance can be checked via
the flue turret/adaptor sample points.
Flue gas sample point location on flue turret/adaptor.
Fig. 69 Combustion test
[1]
Flue gas sample point
[2]
Flue turret flue gas blank plug
[3]
Flue adaptor flue gas blank plug
6.12
Finishing commissioning
6.12.1 Fitting the combustion casing
Fig. 70 Fitting the combustion casing
▶ Ensure this cover is engaged onto top bracket [1] before securing
screw [3].
0010015569-001
1
3
2
0010023566-001
3.
2.
1.