Fault finding and diagnosis
73
Greenstar 4000 – 6 720 891 161 (2020/09)
262
V
System fault boiler electronics / basic
controller
▶ Reset appliance electronics (factory reset).
▶ Check the electrical connections on the board (check for loose wires etc.).
▶ Replace the control unit.
263
V
System fault boiler electronics / basic
controller
▶ Reset appliance electronics (factory reset).
▶ Check the electrical connections on the board (check for loose wires etc.).
▶ Replace the control unit.
265
B
Heat demand lower than energy supplied
Operating message, is not a fault.
• The boiler's ignition sequence alone is sufficient enough to maintain room
temperature.
• The modulating heat demand is higher than the minimum modulation factor of the unit.
The unit switches to proportional control.
268
O
Relay test was activated
Operating message, is not a fault.
• Appliance in component test mode.
269
V
Flame monitoring
▶ Restart the appliance to see if the problem re-occurs.
▶ Check the electrical connections on the board (check for loose wires etc.).
▶ Replace the control unit (PCB).
273
B
Operation of burner and fan interrupted
Operating message, is not a fault.
• The burner and fan have been running continuously for 24 hours and have been shut
down briefly for an appliance electronic inspection
281
B
Pump stuck or running in air
▶ Check primary system water pressure.
▶ Check for air in the system and vent the pump.
▶ Check for circulation within heating system.
▶ Check hydraulic connections to the pump.
▶ Check wiring and operation of the pump, replace if necessary.
283
O
Burner starting
Operating message, is not a fault.
• Burner is starting.
284
O
Opening air/gas ratio control valve/oil
solenoid valves
Operating message, is not a fault.
• Gas valve is opening.
305
O
Boiler in hot water anti-cycle mode
Operating message, is not a fault.
• Anti-cycle mode, domestic hot water post-heat function. Following a domestic hot
water demand the boiler runs for 30 seconds or until the target temperature is met.
– Diverter valve is held in the hot water position for a period of time.
– If no domestic hot water demand is requested then check for false demands on the
cold water inlet.
306
V
Flame signal after closing the fuel supply
Tip: Ensure the working pressure returns immediately to the standing pressure when the
gas valve closes.
▶ Check the gas valve, replace if required.
▶ Check electrodes and connecting leads, replace if required.
▶ Replace the appliance electronics.
353
O
Test non-volatile lockout
Operating message, is not a fault.
• If the boiler has been operating for 24 hours without a 20-minute off period, the boiler
will not respond for a period of time whilst it undertakes diagnostics checks on the fan.
357
O
Flame signal after closing the fuel supply
Operating message, is not a fault.
• Venting/air purge program has been automatically activated.
358
O
Anti-seizing functn. active
Operating message, is not a fault.
• Blocking protection for the heating pump and diverter valve active.
– The purpose of component kick is to ensure that hydraulic components such as
pumps will not get stuck by giving these functional components a “kick”, i.e. they
are briefly turned on after a period of inactivity.
– After power up every 24 hours the appliance will do a component kick, where the
pump will run for 10 seconds.
– If the appliance is already in a CH or DHW heat request, these heat demands will be
prioritised over component kick. But once the heat demand has ended the
component kick will take place.
– If this causes nuisance then please power the appliance off and on again at a more
suitable time; the daily kick will then occur at the time the appliance is turned on
again.
Fa
ult
co
de
Fa
ult
ca
te
go
ry Fault text on the display, description
Remedy