3.4 Flue Connection
The chimney or flue system must comply with the rules in force, and must be a minimum of 125mm in diameter
(5"). The appliance is fitted with a 125mm flue connection, to use a 150mm diameter flue, a reducer will be
required.
The minimum effective flue height for the appliance must be 3 metres. Any horizontal flue run from the rear outlet
must not exceed 100mm from the back of the appliance.
The chimney or flue must be free from any obstruction. Any damper plates must be removed or secured in the fully
open position, and no restrictor plates fitted.
The chimney must be swept prior to the installation, but it need not be swept if it can be seen the chimney is clean
and unobstructed throughout its entire length.
NOTE: If it is intended to fit the appliance into an existing brick built chimney, a 5" (125mm) liner must be used.
Larger lined flues can work, but in some instances could cause cold start flue problems resulting in nuisance
shutdown. Lined flues above 7" (175mm) are not recommended.
Содержание Phoenix 3
Страница 6: ...GB IE 6 2 3 Control Overview 2 3 1 Remote Control...
Страница 7: ...GB IE 7...
Страница 8: ...GB IE 8...
Страница 9: ...GB IE 9...
Страница 10: ...GB IE 10 IF FITTED...
Страница 19: ...GB IE 19 3 6 2 Coal Lay Pack containing 30 Coals...
Страница 20: ...GB IE 20 Position the 30 Coals as shown Coals 1 8 Coals 9 13 Coals 14 17...
Страница 21: ...GB IE 21 Coals 18 22 Coals 23 26 Coals 27 30...
Страница 27: ...GB IE 27 5 3 Dimensions 5 3 1 Phoenix3 Top Flue...
Страница 28: ...GB IE 28 5 3 2 Phoenix3 Rear Flue...
Страница 31: ...GB IE 31...
Страница 33: ...GB IE 33 Appendix 1 Mertik Maxitrol Symax Control System...