G99-Specific Switchgear / Control Settings
For all protection functions that are required by the EREC G99‑1‑6, the respective trip
commands have already been assigned to the circuit breaker »SG[1]«.
SG[1] . Off Cmdx
[Control / SG / SG[1] / Trip Manager]
• SG[1] . Off Cmd1 = V[1] . TripCmd
• SG[1] . Off Cmd2 = V[2] . TripCmd
• SG[1] . Off Cmd3 = V[3] . TripCmd
• SG[1] . Off Cmd4 = V[4] . TripCmd
• SG[1] . Off Cmd5 = V[5] . TripCmd
• SG[1] . Off Cmd6 = V[6] . TripCmd
• SG[1] . Off Cmd7 = f[1] . TripCmd
• SG[1] . Off Cmd8 = f[2] . TripCmd
• SG[1] . Off Cmd9 = f[3] . TripCmd
• SG[1] . Off Cmd10 = df/dt . TripCmd
• SG[1] . Off Cmd11 = Intertripping . TripCmd
Off Command to the Circuit Breaker
if the state of the assigned signal
becomes true.
For the password-protection (of
access level “P.2”), see the
“Security” chapter in the generic
MRU4 User Manual.
P.2
23
MRU4
MRU4-3.6-EN-G99
3 G99-Specific Switchgear / Control Settings